Pepperl+Fuchs NCN3-F31-N4-V1
Inductive sensor

Pepperl+Fuchs NCN3-F31-N4-V1
Series: Rectangular type, Housing material: PBT, Rated operating distance: 3 mm, Connection (system side): 4-pin, M12 x 1 connector, Output type: 2-wire, Installation: flush mountable, Type of voltage: DC, ATEX 3G
Item Number: NCN3-F31-N4-V1
156.60
-
+
Total price: 156.60
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
General specifications
Switching element functionDC Dual NC
Rated operating distance3 mm
Installationflush mountable
Output polarityNAMUR
Assured operating distance0 ... 2.4 mm
Reduction factor rAl 0.35
Reduction factor rCu 0.3
Reduction factor r304 0.75
Reduction factor rSt37 1
Reduction factor rBrass 0.45
Nominal ratings
Nominal voltage8 V
Switching frequency0 ... 3 kHz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detectedgreater or equal 3 mA
Measuring plate detectedless than or equal to 1 mA
Switching state indicatorLED, yellow
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated less than or equal to 36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Note:
Under the same product name but with a different part no., this product has a predecessor with a restricted temperature range (up to +70 °C).
The temperature range specified here (up to +100°C) only applies to sensors with part no. 2239**.
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection (system side)4-pin, M12 x 1 connector
Housing materialPBT
Sensing facePBT
Degree of protectionIP67
General information
Use in the hazardous areasee instruction manuals
Category1G- 2G- 3G

Comments

No comments yet

Write a comment