Pepperl+Fuchs NCN3-F31-N4-V16-V1-Y223960
Inductive sensor

Pepperl+Fuchs NCN3-F31-N4-V16-V1-Y223960
  • Direct mounting on standard actuators
  • Fixed setting
  • EC-Type Examination Certificate TГњV99 ATEX 1479X
  • Usable up to SIL 2 acc. to IEC 61508
Item Number: NCN3-F31-N4-V16-V1-Y223960
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
Actuating elementStainless steel 1.4305 / AISI 303
8.5 mm x 8.5 mm x 0.5 mm
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Effective internal inductancemax. 100 µH
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Sensing facePBT
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Reduction factor rAl 0.5
Connection (system side)V16-connector
Effective internal inductancemax. 100 µH
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Type of protectionintrinsic safety
Connection (valve side)1 connector V1 (M12 x 1)
Time delay before availability≤ 1.1 ms
Housing materialPBT
Currentmax. 240 mA
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Short-circuit protectionyes
CE marking[*PD-Z02585A*]
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 15 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 75 В°C (167 В°F)
T5 : 90 В°C (194 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 75 В°C (167 В°F)
T5 : 90 В°C (194 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 65 В°C (149 В°F)
T5 : 80 В°C (176 В°F)
T4 : 90 В°C (194 В°F)
T3 : 90 В°C (194 В°F)
T2 : 90 В°C (194 В°F)
T1 : 90 В°C (194 В°F)
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Ambient temperature-25 ... 100 В°C (-13 ... 212 В°F)
Note:
Under the same product name but with a different part no., this product has a predecessor with a restricted temperature range (up to +70 В°C).
The temperature range specified here (up to +100В°C) only applies to sensors with part no. 2239**.
Effective internal inductancemax. 100 µH
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
UL approvalcULus Listed, General Purpose
Reverse polarity protectionreverse polarity protected
Output type2-wire
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Reduction factor rSt37 1.3
Type of protectionintrinsic safety
Voltagemax. 32 V DC
Short-circuit protectionno
MTTFd1470 a
Switching state indicatorLED, yellow
Effective internal inductancemax. 100 µH
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
CE marking[*PD-Z02586A*]
Degree of protectionIP67
Actual operating distance2.7 ... 3.3 mm typ.
Use in the hazardous areasee instruction manuals
CE marking[*PD-Z02585A*]
Hysteresistyp. 5 %
Switching frequency0 ... 3 kHz
Assured operating distance0 ... 2.4 mm
Rated operating distance3 mm
Reduction factor rBrass 0.6
Reduction factor r304 1
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 15 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 52 mA , Pi = 169 mW : 90 В°C (194 В°F)
CSA approvalcCSAus Listed, General Purpose
Output typeNAMUR
Type of protectionintrinsic safety
Switching function2 x normally closed (NC)
Storage temperature-40 ... 100 В°C (-40 ... 212 В°F)
Equipment protection levelGa , Gb , Gc (ic) , Mb
Reduction factor rCu 0.4
Type of protectionintrinsic safety
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Mission Time (TM)20 a
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Installationflush mountable
Nominal voltage8 V
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 20 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 75 В°C (167 В°F)
T5 : 90 В°C (194 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 20 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 75 В°C (167 В°F)
T5 : 90 В°C (194 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 20 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 65 В°C (149 В°F)
T5 : 80 В°C (176 В°F)
T4 : 90 В°C (194 В°F)
T3 : 90 В°C (194 В°F)
T2 : 90 В°C (194 В°F)
T1 : 90 В°C (194 В°F)
Valve status indicatorLED, yellow
Diagnostic Coverage (DC)0 %
CCC approvalCCC approval / marking not required for products rated ≤36 V
CE marking[*PD-Z02585A*]
Safety Integrity Level (SIL)SIL 2
Reverse polarity protectionyes, with reversed output LED is out of function, therfore more power for solenoid valve

Comments

No comments yet

Write a comment