Pepperl+Fuchs NJ1,5-6,5-N-Y10324
Inductive sensor

Pepperl+Fuchs NJ1,5-6,5-N-Y10324
  • Comfort series
Item Number: NJ1,5-6,5-N-Y10324
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
Core cross-section0.14 mm2
CE marking[*PD-Z02585A*]
Effective internal capacitancemax. 30 µF
A cable length of 10 m is considered.
Housing materialStainless steel 1.4305 / AISI 303
Effective internal capacitancemax. 30 nF ; a cable length of 10 m is considered.
Effective internal inductancemax. 50 µH
A cable length of 10 m is considered.
Ambient temperature-25 ... 100 В°C (-13 ... 212 В°F)
Hysteresistyp. %
Assured operating distance0 ... 1.215 mm
Switching frequency0 ... 5000 Hz
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Reduction factor rCu 0.19
Use in the hazardous areasee instruction manuals
CSA approvalcCSAus Listed, General Purpose
Switching functionNormally closed (NC)
Connection typecable PUR , 2 m
Degree of protectionIP67
Appropriate typeNJ 1,5-6,5...-N...
Nominal voltage8 V
Reduction factor r304 0.65
CE marking[*PD-Z02585A*]
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Reduction factor rAl 0.22
UL approvalcULus Listed, General Purpose
Output typeNAMUR
Output type2-wire
Appropriate typeNJ 1,5-6,5...-N...
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Sensing facePBT
ATEX marking II 1D Ex ia IIIC T135В°C Da
The Ex-related marking can also be printed on the enclosed label.
ATEX marking II 2G Ex ia IIC T6…T1 Gb
The Ex-related marking can also be printed on the enclosed label.
Installationflush
Rated operating distance1.5 mm
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Effective internal inductancemax. 50 µH ; a cable length of 10 m is considered.

Comments

No comments yet

Write a comment