Pepperl+Fuchs NJ2-12GK-N-Y40110
Inductive sensor

Pepperl+Fuchs NJ2-12GK-N-Y40110
  • Comfort series
  • 2 mm flush
Item Number: NJ2-12GK-N-Y40110
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
Output typeNAMUR
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
CE marking[*PD-Z02585A*]
Reduction factor rAl 0.4
Effective internal inductancemax. 50 andmicro;H ; a cable length of 10 m is considered.
Reduction factor rCu 0.3
Use in the hazardous areasee instruction manuals
CSA approvalcCSAus Listed, General Purpose
Ambient temperature-25 ... 100 В°C (-13 ... 212 В°F)
MTTFd5887 a
Effective internal capacitancemax. 45 andmicro;F
A cable length of 10 m is considered.
Installationflush
Degree of protectionIP68
Nominal voltage8 V
Diagnostic Coverage (DC)0 %
Core cross-section0.34 mm2
Switching functionNormally closed (NC)
Reduction factor r304 0.85
CE marking[*PD-Z02585A*]
Connection typecable , 150 mm with wire end ferrule
Effective internal capacitancemax. 45 nF ; a cable length of 10 m is considered.
UL approvalcULus Listed, General Purpose
ATEX marking II 1D Ex ia IIIC T135В°C Da
The Ex-related marking can also be printed on the enclosed label.
Rated operating distance2 mm
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Sensing facePBT
Effective internal inductancemax. 50 andmicro;H
A cable length of 10 m is considered.
Assured operating distance0 ... 1.62 mm
Switching frequency0 ... 2000 Hz
ATEX marking II 2G Ex ia IIC T6andhellip;T1 Gb
The Ex-related marking can also be printed on the enclosed label.
Appropriate typeNJ 2-12GK-N...
Mission Time (TM)20 a
Appropriate typeNJ 2-12GK-N...
Output type2-wire
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Housing materialPBT

Comments

No comments yet