Pepperl+Fuchs NJ2-12GM-N-Y10638
Inductive sensor
- Comfort series
- 2 mm flush
- Overview
- Comments
Core cross-section | 0.34 mm2 |
Effective internal inductance | max. 50 µH A cable length of 10 m is considered. |
Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) |
Reduction factor r304 | 0.85 |
Reduction factor rAl | 0.4 |
Housing material | Stainless steel 1.4305 / AISI 303 |
Degree of protection | IP67 |
CSA approval | cCSAus Listed, General Purpose |
Effective internal capacitance | max. 30 µF A cable length of 10 m is considered. |
Installation | flush |
UL approval | cULus Listed, General Purpose |
Reduction factor rCu | 0.3 |
Output type | 2-wire |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
CE marking | [*PD-Z02585A*] |
Switching frequency | 0 ... 2000 Hz |
CE marking | [*PD-Z02585A*] |
Assured operating distance | 0 ... 1.62 mm |
Appropriate type | NJ 2-12GM-N... |
Rated operating distance | 2 mm |
Use in the hazardous area | see instruction manuals |
Output type | NAMUR |
Mission Time (TM) | 20 a |
MTTFd | 5887 a |
ATEX marking | II 2G Ex ia IIC T6…T1 Gb The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Switching function | Normally closed (NC) |
Diagnostic Coverage (DC) | 0 % |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Sensing face | PBT |
ATEX marking | II 1D Ex ia IIIC T135В°C Da The Ex-related marking can also be printed on the enclosed label. |
Appropriate type | NJ 2-12GM-N... |
Nominal voltage | 8 V |
Connection type | cable PUR , 2 m |
Effective internal capacitance | max. 30 nF ; a cable length of 10 m is considered. |
People also buy
Comments