Pepperl+Fuchs NJ8-18GM-N-5M
Inductive sensor
- 8 mm non-flush
- Usable up to SIL 2 acc. to IEC 61508
Item Number:
NJ8-18GM-N-5M
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Nominal voltage | 8 V |
CE marking | [*PD-Z02585A*] |
Reduction factor rCu | 0.3 |
Effective internal capacitance | max. 70 nF ; a cable length of 10 m is considered. |
Effective internal capacitance | max. 70 nF ; a cable length of 10 m is considered. |
Effective internal inductance | max. 50 andmicro;H ; a cable length of 10 m is considered. |
Output type | 2-wire |
Appropriate type | NJ 8-18GM-N... |
Sensing face | PBT |
Rated operating distance | 8 mm |
Use in the hazardous area | see instruction manuals |
Housing material | Stainless steel 1.4305 / AISI 303 |
Assured operating distance | 0 ... 6.48 mm |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Hysteresis | typ. % |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
ATEX marking | II 1G Ex ia IIC T6andhellip;T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Installation | non-flush |
ATEX marking | II 1D Ex ia IIIC T135В°C Da The Ex-related marking can also be printed on the enclosed label. |
Reduction factor r304 | 0.85 |
Appropriate type | NJ 8-18GM-N... |
Effective internal capacitance | max. 70 nF ; a cable length of 10 m is considered. |
CCC approval | CCC approval / marking not required for products rated 36 V |
Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) |
Effective internal inductance | max. 50 andmicro;H ; a cable length of 10 m is considered. |
UL approval | cULus Listed, General Purpose |
CE marking | [*PD-Z02585A*] |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
EAC conformity | TR CU 012/2011 |
Appropriate type | NJ 8-18GM-N... |
Reduction factor rAl | 0.4 |
Connection type | cable PVC , 5 m |
Switching frequency | 0 ... 200 Hz |
Core cross-section | 0.75 mm2 |
Effective internal inductance | max. 50 andmicro;H ; a cable length of 10 m is considered. |
Output type | NAMUR |
Degree of protection | IP67 |
CE marking | [*PD-Z02585A*] |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
ATEX marking | II 1G Ex ia IIC T6andhellip;T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Switching function | Normally closed (NC) |
CSA approval | cCSAus Listed, General Purpose |
People also buy
Comments
No comments yet