Sick FLN-OSSD1100108

Sick FLN-OSSD1100108
  • Ability to cascade 32 sensors with up to 30 m per segment in compliance with performance level e
  • Compatible with sensors from all manufacturers
  • Detailed diagnostic information
Item Number: FLN-OSSD1100108
106.35
-
+
Total price: 106.35
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Specification:

Part Number1061710
Flexi Loop output:To connect a Flexi Loop successor module, or to terminate a Flexi Loop string with the Flexi Loop termination element.
Enclosure rating:IP 65, IP 67 (EN 60529)
Cross-circuit:Monitoring via OSSD device
IO-Link:-
Connection type safety device:Female connector M12, 8-pin
Flexi Loop input:To connect a Flexi Loop predecessor module, or to connect a Flexi Loop string with the safety controller Flexi Soft.
Safety integrity level:SIL3 (IEC 61508)
SILCL3 (EN 62061)
Connection type Flexi Loop output:Female connector M12, 5-pin
Category:Category 4 (EN ISO 13849-1)
Protection class:III (EN 61140)
Shock resistance (single shock):30 g, 11 ms (EN 60068-2-27)
Type of supply voltage:SELV
Safe state in the event of a fault:The sensor cascade has no internal fault detection and is unable to assume a safe state in the event of a fault. Fault detection is performed by the connected safety-related logic unit.
Performance level:PL e (EN ISO 13849-1)
Weight:28 g (± 5 %)
Connection type Flexi Loop input:Male connector M12, 5-pin
Power supply output for external devices:+
Sequence errors:Monitoring via Flexi Loop node
Discrepancy errors:Monitoring via Flexi Loop node
Number of non-safe inputs:1
PFHd:0.76 1E-09 (EN ISO 13849)
Power consumption:45 mA
Shock resistance (continuous shock):10 g, 16 ms (EN 60068-2-64)
Storage temperature:-25 °C ... +70 °C
Short-circuit:Monitoring via OSSD device
Safety device connection:Safety sensor with dual-channel OSSD outputs
Dimensions (W x H x D):68.15 mm x 45 mm x 18 mm
Ambient operating temperature:-25 °C ... +55 °C
Supply voltage Vs:24 V DC (16.8 V DC ... 30 V DC)
Number of non-safe outputs:1
Electromagnetic compatibility (EMC):Class A (EN 61000-6-2, EN 55011)
TM (mission time):20 a (EN ISO 13849)

Comments

No comments yet

Write a comment