Sick UE410-XU3T0

Safety controllers
Sick UE410-XU3T0
217.69 EUR

Specification:

Part Number6035244
Vibration resistance:5 g RMS, 5 Hz ... 500 Hz (EN 60068-2-64)
Finely stranded with ferrules (2x):0.25 mm² ... 0.5 mm²
Category:Category 4 (EN ISO 13849)
Differentiation between man and material (muting):+
AND operation:+
Weight:180 g
TM (mission time):20 a (EN ISO 13849)
Safe state in the event of a fault:The safety-related semiconductor outputs are in the OFF state.
PFHd:2.5 1E-09 (EN ISO 13849)
Safety integrity level:SIL3 (IEC 61508)
SILCL3 (EN 62061)
Number of outputs:2 dual-channel or 4 single-channel
Bypass:+
Protection class housing:IP 40 (EN 60529)
Number of muting sensors:0 ... 2
OR operation:+
Eindrahtig oder feindrahtig (1x):0.14 mm² ... 2.5 mm²
Restart interlock:Manual / automatic (configurable)
Type of voltage supply:PELV or SELV
Climate conditions according to:EN 61131-2 (55 °C ambient operating temperature, 95% rel. humidity)
Power consumption:3 W (DC)
Ripple:≤ 10 %
Electromagnetic compatibility (EMC):Class A (EN 61000-6-2, EN 55011)
Air humidity:15 % ... 95 %, non-condensing
Dimensions (W x H x D):22.5 mm x 96.5 mm x 120.8 mm
Finely stranded with ferrules (1x):0.25 mm² ... 2.5 mm²
Voltage supply:Via A1, A2
Ambient operating temperature:-25 °C ... +55 °C
Enclosure rating terminals:IP 20 (EN 60529)
Protection class:III (EN 61140)
Supply voltage Vs:24 V DC (19.2 V DC ... 30 V DC)
Eindrahtig oder feindrahtig (2x):0.14 mm² ... 0.75 mm²
Connection type:Plug-in screw-type terminals
External device monitoring (EDM):+
Number of inputs:2 dual-channel or 4 single-channel
Performance level:PL e (EN ISO 13849)
Storage temperature:-25 °C ... +70 °C