Siemens LME 22.331 C2BT
Burner control unit

Siemens LME 22.331 C2BT

The Product is not Available now!

Check the Price with the manager.

Burner control unit

Item Number: LME 22.331 C2BT
173.00
-
+
Total price: 173.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

The Product is not Available now!

Check the Price with the manager.

The combustion machine lme 22.331 c2 Landis Gyr - SIEMENS manages the fan burners (single-stage and two-stage) of small and medium capacities. The combustion machine (automatic burner) Siemens LME22.331C2 is designed for a service life of up to 250 thousand start-up cycles, which is approximately 10 years of service when the burner is operated under normal conditions.

Furnace machine LME22.331C2 (electromechanical automatic burner). The combustion manager LME 22.331 C2 starts and monitors 1 or 2-stage gas burners with intermittent operation. Flame monitoring by a QRA ... flame detector with an AGQ3 ... block as well as an ionization electrode and various QRC ... flame sensors (blue) The dimensions of the housing of the LME 22.331C2 burner control unit are interchangeable (identical) to the LMG ... and LGB ...

- Multicolored indication of messages about operations and the presence of flame, failure status
- Undervoltage detector
- Limiting the number of restarts (repetitions)
- Intermittent operation (controlled) after continuous operation for 24 hours
- Remote reset (reset) of the burning machine LME22.331C2
- Digital signal processing with precise control sequence
- The function of testing the air pressure switch at startup and in the work process
The list of models that apply to LME control units ... without flame detector and without basket. LME22.331C2 burner control unit with execution mechanism for 2-stage burners.

Sensorflame detector QRA ... 4 with AGQ3 ... A27
Viewautomatic furnace LME22.331C2
VoltageAC 230 V
Expectation2.5 sec
Pre-purge time30 sec (min)
Safety time3 sec (max)
Ignition Pending2 sec
Waiting for ignition3 sec
BV2 Ignition Timings8 sec
Setting the air pressure alarm time3 sec (min)
Opening time of the SA mechanism12 sec (min)
Closing time of the SA mechanism12 sec (min)