Pepperl+Fuchs FB6210BR

Digital Output
Pepperl+Fuchs FB6210BR
730.66
One click request
Damaging gasEN 60068-2-42
Current limit37 mA
Open loop voltage24.5 V
Relative humidityEN 60068-2-56
Reaction time10 s
Electromagnetic compatibilityNE 21
Interfacemanufacturer-specific bus to standard com unit
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Connectionbackplane bus
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Response time10 ms (depending on bus cycle time)
Number of channels4
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Degree of protectionIEC 60529
LED indicationLED green: supply
LED red: line fault , red flashing: communication error
Shock resistanceEN 60068-2-27
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionchannel I: 9+, 10-; channel II: 11+, 12-; channel III: 13+, 14-; channel IV: 15+, 16-
Connectionbackplane bus / 24 V booster via wire ends
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Vibration resistanceEN 60068-2-6
Occupied slots2
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
ATEX approvalPTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U
Internal resistormax. 370 andOmega;
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
EU-Type Examination CertificatePTB 97 ATEX 1074 U
Massapprox. 750 g
Codingoptional mechanical coding via front socket
Input voltage range18.5 ... 32 V DC (SELV/PELV) booster voltage
Power consumption0.15 W
Rated voltage12 V DC , only in connection with the power supplies FB92**
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Power dissipation3 W
EAC approvalRussia: RU C-IT.MIII06.B.00129
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Line fault detectioncan be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Relative humidity95 % non-condensing
Environmental testEN 60068-2-14
in international format without spaces