Pepperl+Fuchs HiC2877

Solenoid Driver
Pepperl+Fuchs HiC2877
244.78
One click request
Degree of protectionIEC 60529:2001
EU-type examination certificateCESI 10 ATEX 046
Inrush current0.2 A , 15 ms loop powered
Current≤ 40 mA
Mountingon Termination Board
ConnectionSL1: 8a(+), 7a(-) loop powered
SL1: 10a(+), 9a(-) bus powered
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Voltage≥ 11.2 V
Open loop voltageapprox. 22.5 V
Current limit55 mA
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Power dissipation1 W at 24 V, 300 Ω load
Connection sidecontrol side
Control elementsDIP-switch
Energized/De-energized delay- bus powered: filter OFF: 1 ms, filter ON: 10 ms
- loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load)
Switching frequency- bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz
- loop powered: max. 10 Hz
Display elementsLEDs
ConnectionSL1: 6b
Degree of protectionIP20
CertificateKIWA 15 ATEX 0036 X
Control inputexternal switch (dry contact or open collector) non isolated or logic signal input fully floating
Fault levellead short-circuit detection at < 25 Ω
lead breakage detection at > 100 kΩ typical
Labelingspace for labeling at the front
Loadnominal 0.1 ... 5 kΩ
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output typeopen collector transistor (internal fault bus)
Input current62 mA at 24 V, 300 Ω load
Power dissipation1 W at 24 V, 300 Ω load for loop powered
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Configurationvia DIP switches
Codingpin 2 and 3 trimmed
For further information see system description.
Safety Integrity Level (SIL)SIL 3
Rated voltage20.4 ... 30 V DC loop powered
20.4 ... 30 V DC bus powered via Termination Board
ConnectionSL2: 5a(+), 5b(-)
Internal resistorapprox. 280 Ω
Signal typeDigital Output
Massapprox. 100 g
Signal level1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kΩ pull-up)
0-signal: 0...5 V DC or contact open
Fault current4 mA pulsing (20 ms ON, 200 ms OFF)
Connection sidefield side
Output/power supply, inputs, and collective errorsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
in international format without spaces