Pepperl+Fuchs HiD2096

Voltage Repeater
Pepperl+Fuchs HiD2096
672.48
One click request
Configurationvia DIP switches
Ripplein 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms
Bandwidth-0.1 dB at 10 kHz; -1 dB at 20 kHz
Input resistance10 kandOmega; terminals 5a and 7a and terminals 1a and 3b
Mountingon Termination Board
Control elementsDIP-switch
Loadmin. 9 kandOmega;
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Transmission range0 ... -20 V
Voltage0 ... -20 V
Connection sidefield side
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Labelingspace for labeling at the front
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
ConnectionSL2:
5a (common), 5b or 7b (supply -), 7a (input -)
1a (common), 1b or 3a (supply -), 3b (signal -)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Display elementsLED
Output rated operating currentSL2: 5a (common), 5b: > 10 mA at -21 V or > 20 mA at -18 V
SL2: 1a (common), 1b: > 10 mA at -21 V or > 20 mA at -18 V
SL2: 5a (common), 7b: 3.7 В± 0.26 mA, 5.3 В± 0.34 mA or 9.0 В± 0.55 mA, dependent on switch settings (see configuration)
SL2: 1a (common), 3a: 3.7 В± 0.26 mA, 5.3 В± 0.34 mA or 9.0 В± 0.55 mA, dependent on switch settings (see configuration)
Degree of protectionIP20
EU-Type Examination CertificateBASEEFA 11 ATEX 0021X
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Connection sidecontrol side
DeviationDC transfer error (with 10 kandOmega; load) < 10mV
Signal typeAnalog input
Power consumption 2.6 W
Output resistance24 andOmega; typ., 27 andOmega; maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer.
Safety Integrity Level (SIL)SIL 2
Time delay relative to input7.0 В± 0.3 micro/s
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
CertificateBASEEFA 11 ATEX 0022X
Codingpin 2 trimmed
For further information see system description.
Ripplewithin the supply tolerance
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Protection against electrical shockUL 61010-1
Massapprox. 140 g
Degree of protectionIEC 60529
in international format without spaces
All fields are required