Pepperl+Fuchs KFA5-DU-Ex1.D

Switch Amplifier, Timer Relay
Pepperl+Fuchs KFA5-DU-Ex1.D
355.15
One click request

Connectionoutput I: terminals 10, 11, 12 ; output II: terminals 19+, 20-

Input I/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output IIsignal , electronic unit, isolated
Input Iacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Configurationvia operating buttons
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Degree of protectionIP20
Output II/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connection sidecontrol side
Output Isignal , Relay output
Output Iterminals 10, 11, 12 non-intrinsically safe
Rated current35 mA
Input IIreset
Electromagnetic compatibilityNE 21:2006
UL approvalE223772
Connection sidefield side
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Control elementsControl panel
Degree of protectionIEC 60529:2001
Power consumption4 VA
Input Iterminals 1+, 3-: Ex ia
IECEx approvalIECEx TUN 03.0000
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionterminals 23, 24
ConnectionInput I: terminals 1+, 3- ; input II: terminals 13+, 14-
Output IIterminals 19+, 20- non-intrinsically safe
CertificateTГњV 02 ATEX 1885 X
Signal typeDigital Input
Reset/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Rated voltage115 V AC В± 10 %
Massapprox. 300 g
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Output II/resetbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificateTГњV 99 ATEX 1408
Connectionscrew terminals
Display elementsLEDs , display
Output I/power supply and resetreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input IIterminals 13+, 14- non-intrinsically safe
Labelingspace for labeling at the front
in international format without spaces
All fields are required