Pepperl+Fuchs LB5106A

Voltage Converter
Pepperl+Fuchs LB5106A
436.73
One click request
Input resistance100 kandOmega;
EU-Type Examination CertificatePTB 03 ATEX 2042
Smallest span500 mV
LED indicationPower LED (P) green: supply
Status LED (1) red: line fault
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Connectionvoltage input: 5+, 6-
Measurement range0 ... 10 V
Damaging gasEN 60068-2-42
UL approvalE106378
IECEx approvalBVS 09.0037X
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Interfacemanufacturer-specific bus to standard com unit
Shock resistanceEN 60068-2-27
Codingoptional mechanical coding via front socket
Connectionbackplane bus
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Environmental testEN 60068-2-14
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Power consumption0.4 W
Vibration resistanceEN 60068-2-6
Linearity error0.1 %
Relative humidity95 % non-condensing
Conversion timemax. 100 ms
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Rated voltage12 V DC , only in connection with the power supplies LB9***
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Electromagnetic compatibilityNE 21
CertificatePF 08 CERT 1234 X
Relative humidityEN 60068-2-56
Degree of protectionIEC 60529
Massapprox. 90 g
Number of channels1
ATEX approvalPTB 03 ATEX 2042
Degree of protectionIP20 when mounted on backplane
Power dissipation0.4 W
Occupied slots1
Connectionbackplane bus
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
in international format without spaces