Pepperl+Fuchs LB6112ER Digital Output with Shutdown Input

Pepperl+Fuchs LB6112ER
Item Number: LB6112ER
  • 4-channel
  • Outputs Ex ia
  • Installation in Zone 2 or safe area
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown
Price on Request
Quantity
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
ATEX approvalPTB 03 ATEX 2042 X
Reaction time10 s
Power consumption0.15 W
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Power dissipation3 W
Open loop voltage17 V
Line fault detectioncan be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Response time10 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Safety Integrity Level (SIL)SIL 2
Codingoptional mechanical coding via front socket
Connectionchannel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-
Connectionbackplane bus / booster terminals
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Relative humidity95 % non-condensing
Rated voltage12 V DC , only in connection with the power supplies LB9***
Connectionbackplane bus
Shock resistanceEN 60068-2-27
Current limit56 mA
IECEx approvalBVS 09.0037X
Degree of protectionIEC 60529
EU-type examination certificatePTB 03 ATEX 2042 X
CertificatePF 08 CERT 1234 X
Internal resistormax. 185 Ω
Degree of protectionIP20 when mounted on backplane
Vibration resistanceEN 60068-2-6
Environmental testEN 60068-2-14
Relative humidityEN 60068-2-56
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Massapprox. 150 g
Occupied slots2
LED indicationPower LED (P) green: supply
Status LED (I) red: line fault , red flashing: communication error
Number of channels4
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Input voltage range18.5 ... 32 V DC (SELV/PELV) booster voltage
Interfacemanufacturer-specific bus to standard com unit
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Damaging gasEN 60068-2-42
Electromagnetic compatibilityNE 21

Comments

No comments yet

Write a comment