Pepperl+Fuchs M-LB-Ex-5241

Protection Module
Pepperl+Fuchs M-LB-Ex-5241
117.03
One click request
Rated current500 mA , restrictions see derating characteristics
Display elementsLED PWR (power supply), green LED
LED FLT (fault signal), red LED
LED CHK (maintenance signal), yellow LED
Impulse reset time< 500 ms
Connectionprotected area: terminal 4
unprotected area: terminals 1, 2, 3
Voltage protection levelmax. 55 V line-line for nominal discharge current In
max. 1400 V line-earth for nominal discharge current In
Degree of protectionIP20
Number of protected signal lines1
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Signal lines/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Rated surge current (8/20 micro/s)10 kA per line (1x)
Massapprox. 20 g
Degree of protectionIEC 60529:2013
Functional safetyIEC/EN 61508:2010
Status indicationfault and maintenance signal via Universal Power Rail M-UPR-03-S
Mountingpluggable in base module for mounting on 35 mm DIN mounting rail
Surge protective devices for low voltageEN 61643-21:2001+A1:2009+A2:2013
IEC 61643-21:2001+A1:2008+A2:2012
Maximum continuous operating voltage30 V DC
Dimensions6.2 x 77 x 79 mm
Nominal discharge current (8/20 micro/s)5 kA per line (10x)
EU-Type Examination CertificateBVS 17 ATEX E 069 X
Current 8 mA
Safety Integrity Level (SIL)SIL 3
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Impulse discharge current (10/350 micro/s)1 kA per line (2x)
Nominal voltage24 V DC
Leakage current< 3 andmicro;A at 24 V and 25 В°C (77 В°F) , line-line
Ambient temperature-40 ... 60 В°C (-40 ... 140 В°F)
Observe the temperature range limited by derating, see section derating.
Topologynon-grounded
Connectionvia Universal Power Rail M-UPR-03-S
Impulse rating1 kV/0.5 kA (category C1)
10 kV/5 kA (category C2)
1 kA (category D1)
Total discharge current (8/20 micro/s)10 kA (1x)
Signal lines/fault indication outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Relative humiditymax. 95 % , without condensation
Nominal voltagesee power feed module M-LB-5300
Designationsystem components:
- base module with screw terminals M-LB-Ex-5000
- base module with spring terminals M-LB-Ex-5000.SP
- power feed module M-LB-5300
- fault status module M-LB-5400
- maintenance status module M-LB-5500
- universal power rail M-UPR-03-S
- place holder module M-LB-Ex-5900
- separation wall M-UPR-I
Series resistance 0.5 andOmega; per line at 25 В°C (77 В°F)
Insertion loss 0.04 dB, at 0 ... 4 kHz, in 600 andOmega;-System
3 dB, at 0 ... 550 kHz, in 100 andOmega;-System
in international format without spaces