Pepperl+Fuchs NCN50-FP-A2-P4

Inductive sensor
Pepperl+Fuchs NCN50-FP-A2-P4
Price on Request
One click request
General specifications
Switching element functionPNP NO/NC
Rated operating distance50 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 40.5 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Nominal ratings
Operating voltage10 ... 60 V
Switching frequency0 ... 80 Hz
Hysteresistyp. 3 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage dropless than or equal to 3 V
Operating current0 ... 200 mA
Off-state current0 ... 0.5 mA
No-load supply currentless than or equal to 20 mA
Operating voltage indicatorLED, green
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd680 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCertified by China Compulsory Certification (CCC)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typescrew terminals
Core cross-sectionup to 2.5 mm2
Housing materialPBT/base of metal
Sensing facePBT
Degree of protectionIP68
in international format without spaces