Pepperl+Fuchs NJ10-30GK-N-D45 Inductive sensor

Pepperl+Fuchs NJ10-30GK-N-D45
Item Number: NJ10-30GK-N-D45
  • Comfort series
  • 10 mm flush
Price on Request
Quantity
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
ATEX marking II 1D Ex ia IIIC T135В°C Da
The Ex-related marking can also be printed on the enclosed label.
Effective internal capacitancemax. 140 µF
A cable length of 10 m is considered.
Appropriate typeNJ 10-30GK...-N...
Effective internal capacitancemax. 140 nF ; a cable length of 10 m is considered.
Reduction factor r304 0.85
Ambient temperature-25 ... 100 В°C (-13 ... 212 В°F)
Effective internal inductancemax. 100 µH
A cable length of 10 m is considered.
Sensing facePBT
Appropriate typeNJ 10-30GK...-N...
CSA approvalcCSAus Listed, General Purpose
Switching functionNormally closed (NC)
Degree of protectionIP68
Installationflush
Reduction factor rAl 0.4
Reduction factor rCu 0.3
CE marking[*PD-Z02585A*]
Rated operating distance10 mm
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Core cross-section0.75 mm2
Output typeNAMUR
CE marking[*PD-Z02585A*]
CCC approvalCCC approval / marking not required for products rated ≤36 V
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Use in the hazardous areasee instruction manuals
ATEX marking II 2G Ex ia IIC T6…T1 Gb
The Ex-related marking can also be printed on the enclosed label.
MTTFd4560 a
UL approvalcULus Listed, General Purpose
Diagnostic Coverage (DC)0 %
Assured operating distance0 ... 8.1 mm
Housing materialSteel 1.0711, nickel-plated
Output type2-wire
Switching frequency0 ... 300 Hz
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Effective internal inductancemax. 100 µH ; a cable length of 10 m is considered.
Mission Time (TM)20 a
Mass430 g
Connection typecable PVC , 2 m
Nominal voltage8 V

Comments

No comments yet

Write a comment