ABB PSTX470-690-70 PSTX Soft starter


- Softstarter
- Product Code: 1SFC132081M0201
- Overview
- Datasheet
- Alternative numbers
- Comments
Softstarter Product Code: 1SFC132081M0201
SPECIFICATION:
Rated Operational Voltage: 208 … 600 V AC
Rated Control Supply Voltage (Us): 100 … 250 V AC
Rated Control Circuit Voltage (Uc): DC Operation 24 V
Rated Frequency (f): Main Circuit 50/60 Hz
Rated Operational Power - In-Line Connection (Pe): (230 V) 12.5 kW; (400 V) 22 kW; (500 V) 25 kW
Rated Operational Current - In-Line Connection (Ie): 45 A
Rated Operational Power - Inside Delta Connection: at 230 V 25 kW; at 400 V 37 kW; at 500 V 45 kW
Rated Operational Current - Inside Delta Connection: 76 A
Service Factor Percentage: 100 %
Overload Protection: Build-in electronic overload protection
Integrated Electronic Overload: Yes
Adjustable Rated Motor Current Ie: 30 ... 100 %
Starting Capacity at Maximum Rated Current Ie: 4xIe for 10s
Ramp Time: 1 ... 120 second [unit of time]
Initial Voltage During Start: 10 ... 99 %
Step Down Voltage Special Ramp: 100 ... 10 %
Current Limit Function: 1.5 … 7.5 xle
Switch for Inside Delta Connection: Yes
Run Signal Relay: Yes
By-pass Signal Relay: Yes
Fault Signal Relay: Yes
Overload Signal Relay: Yes
Analog Outputs: 0…10 V, 0…20 mA, 4…20 mA
Communication: Built in Modbus interface, Anybus, FieldBusPlug (with adapter).
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Cable Clamp
Connecting Capacity Main Circuit: Hole Diameter 8.5 mm
Connecting Capacity Control Circuit: Rigid 1x2.5 mm²
Connecting Capacity Supply Circuit: Rigid 1x2.5 mm²
Tightening Torque: Main Circuit 8 N·m
Product Main Type: PSTX45
Comments
No comments yet