Endress+Hauser TR12
Modular RTD thermometer

Endress+Hauser TR12

Resistance thermometer

Accuracy

class A acc. to IEC 60751
class AA acc. to IEC 60751

Response time

depending on configuration

Max. process pressure (static)

at 20 В°C: 40 bar (580 psi)

Operating temperature range

PT100 TF StrongSens:
-50 В°C ...500 В°C
(-58 В°F ...932 В°F)
PT100 WW:
-200 В°C ...600 В°C
(-328 В°F ...1.112 В°F)
PT100 TF:
-50 В°C ...400 В°C
(-58 В°F ...752 В°F)

Max. immersion length on request

up to 10.000,00 mm (393,70'')

Item Number: TR12
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments

Modular resistance thermometer. Process connection - compression fitting. For all industries.

Comprehensive and common temperature measurement technology for almost all branches of industry.

Measuring principle

Resistance Temperature Detector

Characteristic / Application

metric style
modular temperature assembly
universal range of application
suitable for hazardous areas
process connection as compression fitting
without neck
incl. thermowell / protection tube (metal)

Thermowell / protection tube

welded protection tube

Insert / probe

mineral insulated (MI), flexible

Outer diameter protection tube / Insert

9,0 mm (0,35'')
11,0 mm (0,43'')
12,0 mm (0,47'')
14,0 mm (0,55")
15,0 mm (0,59")

Max. immersion length on request

up to 10.000,00 mm (393,70'')

Material protection tube/ thermowell

1.4404 (316L)
1.4571 (316Ti)
1.4841 (310)

Optional coating

Not defined

Process connection

compression fitting:
G1/2"
G3/4"
G1"
NPT1/2"
weldingadapter

Tip shape

straight
reduced
tapered

Surface roughness Ra

Not defined

Operating temperature range

PT100 TF StrongSens:
-50 В°C ...500 В°C
(-58 В°F ...932 В°F)
PT100 WW:
-200 В°C ...600 В°C
(-328 В°F ...1.112 В°F)
PT100 TF:
-50 В°C ...400 В°C
(-58 В°F ...752 В°F)

Max. process pressure (static)

at 20 В°C: 40 bar (580 psi)

Accuracy

class A acc. to IEC 60751
class AA acc. to IEC 60751

Response time

depending on configuration

Integration head transmitter

yes (4 ... 20 mA; HART; PROFIBUS PA; FOUNDATION FIELDBUS)

Ex - approvals

ATEX II
ATEX IECEx
NEPSI
IECEx
EAC Ex

Certification

Gost Metrology
SIL (transmitter only)

Comments

No comments yet