Endress+Hauser Omnigrad M TR44
Resistance thermometer
Resistance thermometer
- Overview
- Comments
Resistance thermometer for the food and pharmaceutical industry Omnigrad M. Non-replaceable measuring insert PT100.
Measuring principleResistance Temperature Detector
Characteristic / Applicationmetric style
modular temperature assembly
hygienic design
hygienic process connection
with neck
without (not intended to use with thermowell)
Insert / probemineral insulated (MI), flexible
Outer diameter protection tube / Insert6,0 mm (0,24'')
8,0 mm (0,31'')
up to 1.000,00 mm (39,37'')
Material protection tube/ thermowell1.4435 (316L)
Process connectionhygienic:
conical sealing system G1/2" (metal)
conical sealing system M12x1,5 (metal)
clamp connections acc. to ISO 2852 / DIN 32676
clamp connections TRI-Clamp / Micro-Clamp
screwed pipe joint acc. to DIN 11851
screwed pipe joint acc. to DIN 11864-1
Varivent
SMS 1147/8
G1" Liquiphant type M
Ingold
welded (cylindircal)
welded (spherical)
straight
reduced
0,4 Ојm (15,7 Ојin.)
0,8 Ојm (31,5 Ојin.)
PT 100:
-50 В°C ...200 В°C
(-58 В°F ...392 В°F)
at 20 В°C: 50 bar (725 psi)
Accuracyclass A acc. to IEC 60751
1/3 DIN class B acc. to IEC 60751
depending on configuration
t50 = 5 s
t90 = 13 s
yes (4 ... 20 mA; HART; PROFIBUS PA; FOUNDATION FIELDBUS)
Ex - approvalsATEX
CertificationGost Metrology
FDA
EHEDG
3A
SIL (transmitter only)
Comments
No comments yet