Endress+Hauser TAF11
High temperature TC thermometer
Thermocouple
Accuracyclass 2 acc. to IEC 60584
Max. process pressure (static)at 20 В°C: 1 bar (15 psi)
Operating temperature rangeType K:
-40 C ...1.300 C
(-40 F ...2.372 F)
Type J:
-40 C ...750 C
(-40 F ...1.382 F)
Type N:
-40 C ...1.150 C
(-40 F ...2102 F)
Type S:
0 C ...1.600 C
(32 F ...2.912 F)
Type R:
0 C ...1.600 C
(32 F ...2.912 F)
Type B:
600 C ...1.600 C
(1.112 F ...2.912 F)
up to 4.000,00 mm (157,48'')
- Overview
- Comments
Temperature sensor designed for high temperature applications Omnigrad S. Ceramic thermowell and various process connections. Innovative thermowell materials provide resistance to mechanical and chemical attack.
Applicable for steel treatment (annealing), concrete furnaces and primaries.
Measuring principleThermocouple
Characteristic / Applicationmetric style
modular temperature assembly
high temperature probe (furnace)
incl. single ceramic thermowell
ceramic protection tube
Insert / probeceramic capilarry, rigid
Outer diameter protection tube / Insert14,0 mm (0,55")
16,0 mm (0,59")
17,0 mm (0,68")
22,0 mm (0,87")
24,0 mm (0,94")
26,6 mm (1,05")
up to 4.000,00 mm (157,48'')
Material protection tube/ thermowellCeramic (C610)
silicon nitride ceramic (SiN)
sintered silicon carbide (SiC)
compression fitting:
G3/4"
G1"
G11/2"
adjustable Flange
straight
Operating temperature rangeType K:
-40 C ...1.300 C
(-40 F ...2.372 F)
Type J:
-40 C ...750 C
(-40 F ...1.382 F)
Type N:
-40 C ...1.150 C
(-40 F ...2102 F)
Type S:
0 C ...1.600 C
(32 F ...2.912 F)
Type R:
0 C ...1.600 C
(32 F ...2.912 F)
Type B:
600 C ...1.600 C
(1.112 F ...2.912 F)
at 20 В°C: 1 bar (15 psi)
Accuracyclass 2 acc. to IEC 60584
Integration head transmitteryes (4 ... 20 mA; HART; PROFIBUS PA; FOUNDATION FIELDBUS)
CertificationSIL (transmitter only)
Comments