Endress+Hauser Proline Promass F 300
Coriolis flowmeter
Mass flow (liquid): В±0.10 % (standard), 0.05 % (option)
Volume flow (liquid): В±0.10 %
Mass flow (gas): В±0.25 %
Density (liquid): В±0.0005 g/cmВі
0 to 2 200 000 kg/h (0 to 80 840 lb/min)
Medium temperature rangeStandard: 50 to +150 В°C (58...+302 В°F)
Option: 50 to +240 В°C (58...+464 В°F)
High temperatur option: 50 to +350 В°C (58...+662 В°F)
Option: 196 to +150 В°C (320 to +302 В°F)
PN 100, Class 600, 63K
Wetted materialsMeasuring tube: 1.4539 (904L); 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022)
Connection: 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022); 1.4301 (F304)
- Overview +
- Comments +
Flowmeter with premium accuracy, robustness and a compact, easily accessible transmitter.
Measuring principleCoriolis
Product headlineFlowmeter with premium accuracy, robustness and a compact, easily accessible transmitter.
Highest measurement performance for liquids and gases under varying, demanding process conditions.
Highest process safety immune to fluctuating and harsh environments. Fewer process measuring points multivariable measurement (flow, density, temperature). Space...saving installation no in-/outlet run needs.
Mass flow: measurement error В±0.05 % (PremiumCal). Medium temperature: 196 to 350 В°C (320 to 662 В°F). Nominal diameter: DN 8 to 250 (ВівЃ„в‚€ to 10").
Full access to process and diagnostic information numerous, freely combinable I/Os and fieldbuses. Reduced complexity and variety freely configurable I/O functionality. Integrated verification Heartbeat Technology.
Compact dual-compartment housing with up to 3 I/Os. Backlit display with touch control and WLAN access. Remote display available.
DN 8 to 250 (в…њ to 10")
Wetted materialsMeasuring tube: 1.4539 (904L); 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022)
Connection: 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022); 1.4301 (F304)
Mass flow, density, temperature, volume flow, corrected volume flow, reference density, concentration
Max. measurement errorMass flow (liquid): В±0.10 % (standard), 0.05 % (option)
Volume flow (liquid): В±0.10 %
Mass flow (gas): В±0.25 %
Density (liquid): В±0.0005 g/cmВі
0 to 2 200 000 kg/h (0 to 80 840 lb/min)
Max. process pressurePN 100, Class 600, 63K
Medium temperature rangeStandard: 50 to +150 В°C (58...+302 В°F)
Option: 50 to +240 В°C (58...+464 В°F)
High temperatur option: 50 to +350 В°C (58...+662 В°F)
Option: 196 to +150 В°C (320 to +302 В°F)
Standard: 40 to +60 В°C (40 to +140 В°F)
Option: 50 to +60 В°C (58 to +140 В°F)
Standard: 1.4301 (304)
Option: 1.4404 (316/316L)
AlSi10Mg, coated; 1.4409 (CF3M) similar to 316L; stainless steel for hygenic transmitter design
Degree of protectionCompact version: IP66/67, type 4X enclosure.
External WLAN antenna: IP67
IP69
4-line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
3 outputs:
4-20 mA HART (active/passive)
4-20 mA WirelessHART
4-20 mA (active/passive)
Pulse/frequency/switch output (active/passive)
Double pulse output (active/passive)
Relay output
Status input
4-20 mA input
HART, PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, Modbus RS485, Profinet, Ethernet/IP, OPC-UA
Power supplyDC 24 V
AC 100 to 230 V
AC 100 to 230 V / DC 24 V (non-hazardous area)
ATEX, IECEx, cCSAus, NEPSI, INMETRO, EAC, UK Ex
Product safetyCE, C-tick, EAC marking
Functional safetyFunctional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Metrological approvals and certificatesCalibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Heartbeat Technology complies with the requirements for measurement traceability according to ISO 9001:2015 Section 7.1.5.2 a (TГњV SГњD attestation)
MI-005 (Liquids other than water, Hydrocarbons, LPG, cryogenic liquids)
NTEP (Liquids other than water, LPG, cryogenic liquids)
MC (Liquids other than water, cryogenic liquids)
MI-002, PTB
LR approval, DNV GL approval, ABS approval, BV approval, CCS approval
Pressure approvals and certificatesPED, CRN, AD 2000
Material certificates3.1 material
NACE MR0175/MR0103, PMI; welding test acc. to EN ISO, ASME, NORSOK
3-A, EHEDG, cGMP
Measuring principleCoriolis
Product HeadlineFlowmeter with premium accuracy, robustness and a compact, easily accessible transmitter.
Highest measurement performance for liquids and gases under varying, demanding process conditions.
Highest process safety immune to fluctuating and harsh environments. Fewer process measuring points multivariable measurement (flow, density, temperature). Space...saving installation no in-/outlet run needs.
Mass flow: measurement error В±0.05 % (PremiumCal). Medium temperature: 196 to 350 В°C (320 to 662 В°F). Nominal diameter: DN 8 to 250 (ВівЃ„в‚€ to 10").
Full access to process and diagnostic information numerous, freely combinable I/Os and fieldbuses. Reduced complexity and variety freely configurable I/O functionality. Integrated verification Heartbeat Technology.
Compact dual-compartment housing with up to 3 I/Os. Backlit display with touch control and WLAN access. Remote display available.
DN 8 to 250 (в…њ to 10")
Wetted materialsMeasuring tube: 1.4539 (904L); 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022)
Connection: 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022); 1.4301 (F304)
Mass flow, density, temperature, volume flow, corrected volume flow, reference density, concentration
Max. measurement errorMass flow (liquid): В±0.10 % (standard), 0.05 % (option)
Volume flow (liquid): В±0.10 %
Mass flow (gas): В±0.25 %
Density (liquid): В±0.0005 g/cmВі
0 to 2 200 000 kg/h (0 to 80 840 lb/min)
Max. process pressurePN 100, Class 600, 63K
Medium temperature rangeStandard: 50 to +150 В°C (58 to +302 В°F)
Option: 50 to +240 В°C (58 to +464 В°F)
High temperatur option: 50 to +350 В°C (58 to +662 В°F)
Option: 196 to +150 В°C (320 to +302 В°F)
Standard: 40 to +60 В°C (40 to +140 В°F)
Option: 50 to +60 В°C (58 to +140 В°F)
Standard: 1.4301 (304)
Option: 1.4404 (316/316L)
AlSi10Mg, coated; 1.4409 (CF3M) similar to 316L; stainless steel for hygenic transmitter design
Degree of protectionCompact version: IP66/67, type 4X enclosure.
External WLAN antenna: IP67
IP69
4-line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
3 outputs:
4-20 mA HART (active/passive)
4-20 mA WirelessHART
4-20 mA (active/passive)
Pulse/frequency/switch output (active/passive)
Double pulse output (active/passive)
Relay output
Status input
4-20 mA input
HART, PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, Modbus RS485, Profinet, Ethernet/IP, OPC-UA
Power supplyDC 24 V
AC 100 to 230 V
AC 100 to 230 V / DC 24 V (non-hazardous area)
ATEX, IECEx, cCSAus, NEPSI, INMETRO, EAC, UK Ex
Measuring principleCoriolis
Product headlineFlowmeter with premium accuracy, robustness and a compact, easily accessible transmitter.
Highest measurement performance for liquids and gases under varying, demanding process conditions.
Highest process safety immune to fluctuating and harsh environments. Fewer process measuring points multivariable measurement (flow, density, temperature). Space...saving installation no in-/outlet run needs.
Mass flow: measurement error В±0.05 % (PremiumCal). Medium temperature: 196 to 350 В°C (320 to 662 В°F). Nominal diameter: DN 8 to 250 (ВівЃ„в‚€ to 10").
Full access to process and diagnostic information numerous, freely combinable I/Os and fieldbuses. Reduced complexity and variety freely configurable I/O functionality. Integrated verification Heartbeat Technology.
Compact dual-compartment housing with up to 3 I/Os. Backlit display with touch control and WLAN access. Remote display available.
DN 8 to 250 (в…њ to 10")
Wetted materialsMeasuring tube: 1.4539 (904L); 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022)
Connection: 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022); 1.4301 (F304)
Mass flow, density, temperature, volume flow, corrected volume flow, reference density, concentration
Max. measurement errorMass flow (liquid): В±0.10 % (standard), 0.05 % (option)
Volume flow (liquid): В±0.10 %
Mass flow (gas): В±0.25 %
Density (liquid): В±0.0005 g/cmВі
0 to 2 200 000 kg/h (0 to 80 840 lb/min)
Max. process pressurePN 100, Class 600, 63K
Medium temperature rangeStandard: 50 to +150 В°C (58 to +302 В°F)
Option: 50 to +240 В°C (58 to +464 В°F)
High temperatur option: 50 to +350 В°C (58 to +662 В°F)
Option: 196 to +150 В°C (320 to +302 В°F)
Standard: 40 to +60 В°C (40 to +140 В°F)
Option: 50 to +60 В°C (58 to +140 В°F)
Standard: 1.4301 (304)
Option: 1.4404 (316/316L)
AlSi10Mg, coated; 1.4409 (CF3M) similar to 316L; stainless steel for hygenic transmitter design
Degree of protectionCompact version: IP66/67, type 4X enclosure.
External WLAN antenna: IP67
IP69
4-line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
3 outputs:
4-20 mA HART (active/passive)
4-20 mA WirelessHART
4-20 mA (active/passive)
Pulse/frequency/switch output (active/passive)
Double pulse output (active/passive)
Relay output
Status input
4-20 mA input
HART, PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, Modbus RS485, Profinet, Ethernet/IP, OPC-UA
Power supplyDC 24 V
AC 100 to 230 V
AC 100 to 230 V / DC 24 V (non-hazardous area)
ATEX, IECEx, cCSAus, NEPSI, INMETRO, EAC, UK Ex
Product safetyCE, C-tick, EAC marking
Functional safetyFunctional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Metrological approvals and certificatesCalibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Heartbeat Technology complies with the requirements for measurement traceability according to ISO 9001:2015 Section 7.1.5.2 a (TГњV SГњD attestation)
MI-005 (Liquids other than water, Hydrocarbons, LPG, cryogenic liquids)
NTEP (Liquids other than water, LPG, cryogenic liquids)
MC (Liquids other than water, cryogenic liquids)
MI-002, PTB
LR approval, DNV GL approval, ABS approval, BV approval, CCS approval
Pressure approvals and certificatesPED, CRN, AD 2000
Material certificates3.1 material
NACE MR0175/MR0103, PMI; welding test acc. to EN ISO, ASME, NORSOK
3-A, EHEDG, cGMP
Measuring principleCoriolis
Product headlineFlowmeter with premium accuracy, robustness and a compact, easily accessible transmitter.
Highest measurement performance for liquids and gases under varying, demanding process conditions.
Highest process safety immune to fluctuating and harsh environments. Fewer process measuring points multivariable measurement (flow, density, temperature). Space...saving installation no in-/outlet run needs.
Mass flow: measurement error В±0.05 % (PremiumCal). Medium temperature: 196 to 350 В°C (320 to 662 В°F). Nominal diameter: DN 8 to 250 (ВівЃ„в‚€ to 10").
Full access to process and diagnostic information numerous, freely combinable I/Os and fieldbuses. Reduced complexity and variety freely configurable I/O functionality. Integrated verification Heartbeat Technology.
Compact dual-compartment housing with up to 3 I/Os. Backlit display with touch control and WLAN access. Remote display available.
DN 8 to 250 (в…њ to 10")
Wetted materialsMeasuring tube: 1.4539 (904L); 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022)
Connection: 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022); 1.4301 (F304)
Mass flow, density, temperature, volume flow, corrected volume flow, reference density, concentration
Max. measurement errorMass flow (liquid): В±0.10 % (standard), 0.05 % (option)
Volume flow (liquid): В±0.10 %
Mass flow (gas): В±0.25 %
Density (liquid): В±0.0005 g/cmВі
0 to 2 200 000 kg/h (0 to 80 840 lb/min)
Max. process pressurePN 100, Class 600, 63K
Medium temperature rangeStandard: 50 to +150 В°C (58 to +302 В°F)
Option: 50 to +240 В°C (58 to +464 В°F)
High temperatur option: 50 to +350 В°C (58 to +662 В°F)
Option: 196 to +150 В°C (320 to +302 В°F)
Standard: 40 to +60 В°C (40 to +140 В°F)
Option: 50 to +60 В°C (58 to +140 В°F)
Standard: 1.4301 (304)
Option: 1.4404 (316/316L)
AlSi10Mg, coated; 1.4409 (CF3M) similar to 316L; stainless steel for hygenic transmitter design
Degree of protectionCompact version: IP66/67, type 4X enclosure.
External WLAN antenna: IP67
IP69
4-line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
3 outputs:
4-20 mA HART (active/passive)
4-20 mA WirelessHART
4-20 mA (active/passive)
Pulse/frequency/switch output (active/passive)
Double pulse output (active/passive)
Relay output
Status input
4-20 mA input
HART, PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, Modbus RS485, Profinet, Ethernet/IP, OPC-UA
Power supplyDC 24 V
AC 100 to 230 V
AC 100 to 230 V / DC 24 V (non-hazardous area)
ATEX, IECEx, cCSAus, NEPSI, INMETRO, EAC, UK Ex
Product safetyCE, C-tick, EAC marking
Functional safetyFunctional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Metrological approvals and certificatesCalibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Heartbeat Technology complies with the requirements for measurement traceability according to ISO 9001:2015 Section 7.1.5.2 a (TГњV SГњD attestation)
MI-005 (Liquids other than water, Hydrocarbons, LPG, cryogenic liquids)
NTEP (Liquids other than water, LPG, cryogenic liquids)
MC (Liquids other than water, cryogenic liquids)
MI-002, PTB
LR approval, DNV GL approval, ABS approval, BV approval, CCS approval
Pressure approvals and certificatesPED, CRN, AD 2000
Material certificates3.1 material
NACE MR0175/MR0103, PMI; welding test acc. to EN ISO, ASME, NORSOK
3-A, EHEDG, cGMP
Measuring principleCoriolis
Product headlineFlowmeter with premium accuracy, robustness and a compact, easily accessible transmitter.
Highest measurement performance for liquids and gases under varying, demanding process conditions.
Highest process safety immune to fluctuating and harsh environments. Fewer process measuring points multivariable measurement (flow, density, temperature). Space...saving installation no in-/outlet run needs.
Mass flow: measurement error В±0.05 % (PremiumCal). Medium temperature: 196 to 350 В°C (320 to 662 В°F). Nominal diameter: DN 8 to 250 (ВівЃ„в‚€ to 10").
Full access to process and diagnostic information numerous, freely combinable I/Os and fieldbuses. Reduced complexity and variety freely configurable I/O functionality. Integrated verification Heartbeat Technology.
Compact dual-compartment housing with up to 3 I/Os. Backlit display with touch control and WLAN access. Remote display available.
DN 8 to 250 (в…њ to 10")
Wetted materialsMeasuring tube: 1.4539 (904L); 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022)
Connection: 1.4404 (316/316L); Alloy C22, 2.4602 (UNS N06022); 1.4301 (F304)
Mass flow, density, temperature, volume flow, corrected volume flow, reference density, concentration
Max. measurement errorMass flow (liquid): В±0.10 % (standard), 0.05 % (option)
Volume flow (liquid): В±0.10 %
Mass flow (gas): В±0.25 %
Density (liquid): В±0.0005 g/cmВі
0 to 2 200 000 kg/h (0 to 80 840 lb/min)
Max. process pressurePN 100, Class 600, 63K
Medium temperature rangeStandard: 50 to +150 В°C (58 to +302 В°F)
Option: 50 to +240 В°C (58 to +464 В°F)
High temperatur option: 50 to +350 В°C (58 to +662 В°F)
Option: 196 to +150 В°C (320 to +302 В°F)
Standard: 40 to +60 В°C (40 to +140 В°F)
Option: 50 to +60 В°C (58 to +140 В°F)
Standard: 1.4301 (304)
Option: 1.4404 (316/316L)
AlSi10Mg, coated; 1.4409 (CF3M) similar to 316L; stainless steel for hygenic transmitter design
Degree of protectionCompact version: IP66/67, type 4X enclosure.
External WLAN antenna: IP67
IP69
4-line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
3 outputs:
4-20 mA HART (active/passive)
4-20 mA WirelessHART
4-20 mA (active/passive)
Pulse/frequency/switch output (active/passive)
Double pulse output (active/passive)
Relay output
Status input
4-20 mA input
HART, PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, Modbus RS485, Profinet, Ethernet/IP, OPC-UA
Power supplyDC 24 V
AC 100 to 230 V
AC 100 to 230 V / DC 24 V (non-hazardous area)
ATEX, IECEx, cCSAus, NEPSI, INMETRO, EAC, UK Ex
Product safetyCE, C-tick, EAC marking
Functional safetyFunctional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Metrological approvals and certificatesCalibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Heartbeat Technology complies with the requirements for measurement traceability according to ISO 9001:2015 Section 7.1.5.2 a (TГњV SГњD attestation)
MI-005 (Liquids other than water, Hydrocarbons, LPG, cryogenic liquids)
NTEP (Liquids other than water, LPG, cryogenic liquids)
MC (Liquids other than water, cryogenic liquids)
MI-002, PTB
LR approval, DNV GL approval, ABS approval, BV approval, CCS approval
Pressure approvals and certificatesPED, CRN, AD 2000
Material certificates3.1 material
NACE MR0175/MR0103, PMI; welding test acc. to EN ISO, ASME, NORSOK
3-A, EHEDG, cGMP
Buy Endress+Hauser Proline Promass F 300 with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com offers industrial control components. A variety of product types and sizes is available in our web catalog. All your ordered products can be sent in one delivery. We offer a price match guarantee. You can pay for multiple offers with one payment. With each day we gain more and more experience and that's why we are able to satisfy your needs for spare parts.