Endress+Hauser Prosonic FMU41
Ultrasonic measurement Time-of-Flight

Endress+Hauser Prosonic FMU41

Ultrasonic Level Gauge

Accuracy

+/- 2 mm or +/- 0,2 % of set measuring range

Process temperature

-40 В°C ... 80 В°C
(-40 В°F ... 176 В°F)

Process pressure / max. overpressure limit

0.7 bar ... 3 bar abs
(10 psi ... 44 psi)

Max. measurement distance

Liquids: 8 m (26 ft),
Solids: 3.5 m (11 ft)

Main wetted parts

PVDF

Item Number: Prosonic FMU41
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments

Prosonic M FMU41 is Compact non-contact ultrasonic level sensor. Designed to measure the level of liquid products, pastes and coarse bulk solids.

Cost effective device for sophisticated level measurement in liquids and bulk solids for up to 8m.

Measuring principle

Ultrasonic

Characteristic / Application

Compact ultrasonic transmitter

Supply / Communication

2-wire HART

Accuracy

+/- 2 mm or +/- 0,2 % of set measuring range

Ambient temperature

-40 В°C ... 80 В°C
(-40 В°F ... 176 В°F)

Process temperature

-40 В°C ... 80 В°C
(-40 В°F ... 176 В°F)

Process pressure / max. overpressure limit

0.7 bar ... 3 bar abs
(10 psi ... 44 psi)

Main wetted parts

PVDF

Process connection

G / NPT 2"

Blocking distance

0.35 m (1.15 ft)

Max. measurement distance

Liquids: 8 m (26 ft),
Solids: 3.5 m (11 ft)

Communication

4...20 mA HART

Certificates / Approvals

ATEX, FM, CSA, TIIS, INMETRO, NEPSI

Application limits

For higher resistance:
FMU42/FDU9x
Foam / high turbulence possible:
FMU42/FDU91
Fast filling and discharging rate:
FMU90 + FDU9x
Level limit detection:
FMU90 + FDU9x

Measuring principle

Ultrasonic

Product headline

Compact ultrasonic measuring instrument
Cost effective solution for open channels

Max. measurement error

Low accuracy

Measuring range

Measuring distance 0,4...8m [1.3...26ft]

Max. process pressure

atm.

Medium temperature range

-40В°C...80В°C
(-40В°F...176В°F)

Degree of protection

IP68

Outputs

4...20mA(Hart),PA,FF

Inputs

2-wire 16-36V DC
4-wire 16-36V DC
90-253V AC 50/60Hz

Digital communication

PROFIBUS PA, FOUNDATION Fieldbus

Hazardous area approvals

ATEX, FM, CSA

Measuring principle

Ultrasonic

Characteristic / Application

Compact ultrasonic transmitter

Supply / Communication

2-wire HART

Accuracy

+/- 2 mm or +/- 0,2 % of set measuring range 1)

Ambient temperature

-40 В°C ... 80 В°C
(-40 В°F ... 176 В°F)

Process temperature

-40 В°C ... 80 В°C
(-40 В°F ... 176 В°F)

Process pressure / max. overpressure limit

0.7 bar ... 3 bar abs
(10 psi ... 44 psi)

Main wetted parts

PVDF

Process connection

G / NPT 2"

Blocking distance

0.35 m (1.15 ft)

Max. measurement distance

Liquids: 8 m (26 ft),
Solids: 3.5 m (11 ft)

Communication

4...20 mA HART

Certificates / Approvals

ATEX, FM, CSA, TIIS, INMETRO, NEPSI

Application limits

Take notice of range diagram

Comments

No comments yet