CPX-AP-I-4DI4DO-M8-3P Datasheet:
Dimensions (W x L x H) | 30 x 170 x 35 mm |
Type of mounting | On H-rail via accessoriesWith through-hole |
Product weight | 129 g |
Ambient temperature | -20 °C ... 50 °C |
Storage temperature | -40 °C ... 70 °C |
Relative air humidity | 5 - 95%Non-condensing |
Degree of protection | IP65IP67 |
Note on degree of protection | Unused connections sealed |
Corrosion resistance class CRC | 1 - Low corrosion stress |
Max. cable length | 30 m outputs30 m inputs50 m system communication |
Note on max. cable length | Power supply according to nominal voltage |
LABS (PWIS) conformity | VDMA24364-B2-L |
CE mark (see declaration of conformity) | To EU EMC Directive |
CE marking (see declaration of conformity) | To UK instructions for EMC |
KC mark | KC-EMV |
Approval | RCM trademarkc UL us listed (OL) |
Certificate issuing authority | UL E239998 |
Note on materials | RoHS-compliant |
Material housing | PAPCDie-cast zinc, nickel-plated |
Material o-ring | FPM |
Diagnostics via LED | Diagnostics per moduleLoad power supplyStatus per channel |
Diagnostics per internal communication | Load switch-offShort-circuit/overload in output signalShort circuit/overload in sensor supplyElectronics/sensors overvoltageLoad overvoltageElectronics/sensors undervoltageLoad undervoltage |
Number of outputs | 4 |
Communication interface, function | System communication XF10 IN / XF20 OUT |
Communication interface, connection type | 2x socket |
Communication interface, connection technology | M8x1, D-coded according to EN 61076-2-114 |
Communication interface, number of pins/wires | 4 |
Communication interface, protocol | AP |
Communication interface, shielding | yes |
Power supply, function | Incoming electronics/sensors and load |
Power supply, connection type | Plugs |
power supply, connection system | M8x1, A-coded to EN 61076-2-104 |
Power supply, number of pins/wires | 4 |
Power transmission, function | Outgoing electronics/sensors and load |
Power transmission, connection type | Socket |
Power transmission, connection technology | M8x1, A-coded to EN 61076-2-104 |
Power transmission, number of pins/wires | 4 |
Note regarding operating voltage | SELV/PELV fixed power supplies requiredNote voltage drop |
Nominal operating voltage DC of load | 24 V |
Permissible voltage fluctuation of load | ± 25 % |
Nominal DC operating voltage, electronics/sensors | 24 V |
Permissible voltage fluctuations for electronics/sensors | ± 25% |
Max. power supply | 2 x 4 A (external fuse required) |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 35 mA |
Intrinsic current consumption at nominal operating voltage load | Typically 10 mA |
Power failure bridging | 10 ms |
Reverse polarity protection | yes |
Electrical connection input, function | Digital input |
Electrical connection input, connection type | 4x socket |
Electrical connection input, connector system | M8x1, A-coded to EN 61076-2-104 |
Electrical connection input, number of connections/cores | 3 |
Number of inputs | 4 |
Characteristic for inputs | To IEC 61131-2, type 3 |
Switching level | Signal 0: <= 5 VSignal 1: >= 11 V |
Switching logic for inputs | PNP (positive switching)2-wire sensors to IEC 61131-23-wire sensors to IEC 61131-2 |
Input debounce time | 0.1 ms3 ms10 ms20 ms |
Fuse protection of inputs (short circuit) | Internal electronic fuse per module |
Max. residual current of inputs per module | 1.8 A |
Electrical isolation of inputs between channels | no |
Electrical isolation of inputs between channel - internal communication | yes |
Electrical connection output, function | Digital output |
Electrical connection output, connection type | 4x socket |
Electrical connection output, connector system | M8x1, A-coded to EN 61076-2-104 |
Electrical connection output, number of connections/cores | 3 |
Characteristic for outputs | According to IEC 61131-2, type 0.5 |
Switching logic for outputs | PNP (positive switching) |
Fuse protection of outputs (short circuit) | Internal electronic fuse per channel |
Output delay with ohmic load | Signal change 0->1: < 200 µsSignal change 1->0: < 200 µs |
Max. residual current outputs per module | 2 A |
Electrical isolation of outputs between channels | no |
Electrical isolation of outputs between channel - internal communication | yes |
Max. power supply per channel | 0.5 A |
Buy Festo CPX-AP-I-4DI4DO-M8-3P with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com provides top-quality industrial control components. Our online catalog features a wide range of products to meet your specific requirements. Enjoy the convenience of consolidated shipments and competitive pricing. Join our satisfied customers who rely on us for their automation solutions.