Festo CPX-AP-I-4DI4DO-M8-3P
Remote I/O and network interface component
We ship to United States of America!
Festo CPX-AP-I
Item Number:
CPX-AP-I-4DI4DO-M8-3P
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Festo CPX-AP-I Remote I/O and network interface component.
CPX-AP-I-4DI4DO-M8-3P Datasheet:
Dimensions (W x L x H) | 30 x 170 x 35 mm |
Type of mounting | On H-rail via accessoriesWith through-hole |
Product weight | 129 g |
Ambient temperature | -20 °C ... 50 °C |
Storage temperature | -40 °C ... 70 °C |
Relative air humidity | 5 - 95%Non-condensing |
Degree of protection | IP65IP67 |
Note on degree of protection | Unused connections sealed |
Corrosion resistance class CRC | 1 - Low corrosion stress |
Max. cable length | 30 m outputs30 m inputs50 m system communication |
Note on max. cable length | Power supply according to nominal voltage |
LABS (PWIS) conformity | VDMA24364-B2-L |
CE mark (see declaration of conformity) | To EU EMC Directive |
CE marking (see declaration of conformity) | To UK instructions for EMC |
KC mark | KC-EMV |
Approval | RCM trademarkc UL us listed (OL) |
Certificate issuing authority | UL E239998 |
Note on materials | RoHS-compliant |
Material housing | PAPCDie-cast zinc, nickel-plated |
Material o-ring | FPM |
Diagnostics via LED | Diagnostics per moduleLoad power supplyStatus per channel |
Diagnostics per internal communication | Load switch-offShort-circuit/overload in output signalShort circuit/overload in sensor supplyElectronics/sensors overvoltageLoad overvoltageElectronics/sensors undervoltageLoad undervoltage |
Number of outputs | 4 |
Communication interface, function | System communication XF10 IN / XF20 OUT |
Communication interface, connection type | 2x socket |
Communication interface, connection technology | M8x1, D-coded according to EN 61076-2-114 |
Communication interface, number of pins/wires | 4 |
Communication interface, protocol | AP |
Communication interface, shielding | yes |
Power supply, function | Incoming electronics/sensors and load |
Power supply, connection type | Plugs |
power supply, connection system | M8x1, A-coded to EN 61076-2-104 |
Power supply, number of pins/wires | 4 |
Power transmission, function | Outgoing electronics/sensors and load |
Power transmission, connection type | Socket |
Power transmission, connection technology | M8x1, A-coded to EN 61076-2-104 |
Power transmission, number of pins/wires | 4 |
Note regarding operating voltage | SELV/PELV fixed power supplies requiredNote voltage drop |
Nominal operating voltage DC of load | 24 V |
Permissible voltage fluctuation of load | ± 25 % |
Nominal DC operating voltage, electronics/sensors | 24 V |
Permissible voltage fluctuations for electronics/sensors | ± 25% |
Max. power supply | 2 x 4 A (external fuse required) |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 35 mA |
Intrinsic current consumption at nominal operating voltage load | Typically 10 mA |
Power failure bridging | 10 ms |
Reverse polarity protection | yes |
Electrical connection input, function | Digital input |
Electrical connection input, connection type | 4x socket |
Electrical connection input, connector system | M8x1, A-coded to EN 61076-2-104 |
Electrical connection input, number of connections/cores | 3 |
Number of inputs | 4 |
Characteristic for inputs | To IEC 61131-2, type 3 |
Switching level | Signal 0: <= 5 VSignal 1: >= 11 V |
Switching logic for inputs | PNP (positive switching)2-wire sensors to IEC 61131-23-wire sensors to IEC 61131-2 |
Input debounce time | 0.1 ms3 ms10 ms20 ms |
Fuse protection of inputs (short circuit) | Internal electronic fuse per module |
Max. residual current of inputs per module | 1.8 A |
Electrical isolation of inputs between channels | no |
Electrical isolation of inputs between channel - internal communication | yes |
Electrical connection output, function | Digital output |
Electrical connection output, connection type | 4x socket |
Electrical connection output, connector system | M8x1, A-coded to EN 61076-2-104 |
Electrical connection output, number of connections/cores | 3 |
Characteristic for outputs | According to IEC 61131-2, type 0.5 |
Switching logic for outputs | PNP (positive switching) |
Fuse protection of outputs (short circuit) | Internal electronic fuse per channel |
Output delay with ohmic load | Signal change 0->1: < 200 µsSignal change 1->0: < 200 µs |
Max. residual current outputs per module | 2 A |
Electrical isolation of outputs between channels | no |
Electrical isolation of outputs between channel - internal communication | yes |
Max. power supply per channel | 0.5 A |
Buy Festo CPX-AP-I-4DI4DO-M8-3P with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com provides top-quality industrial control components. Our online catalog features a wide range of products to meet your specific requirements. Enjoy the convenience of consolidated shipments and competitive pricing. Join our satisfied customers who rely on us for their automation solutions.
People also buy
Comments
No comments yet