Pepperl+Fuchs 5500-MAN-CDUL-24VDC
5500 series manifold

Pepperl+Fuchs 5500-MAN-CDUL-24VDC
  • Suitable for Class I, II/Div. 2 for hazardous locations
  • Certified for UL CSA
  • Manifold combines the solenoid valve for purging and needle valve for pressurization in one housing
  • Suitable for steel or plastic tubing
  • Mounting hardware, pneumatic fittings and tubing included
Item Number: 5500-MAN-CDUL-24VDC
911.24
-
+
Total price: 911.24
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Degree of protectiontype 7 & 9

Connection typePneumatic
Input port: 3/8 inch Tube compression fitting
Output port: 3/8"" Tube compression fitting

Electrical connection
ВЅ"" NPTF thread connection w/ 24"" (0.61m) flying leads
Purge flow ratesolenoid valves : Cv (flow coefficient) = 1.4
needle valve : Cv (flow coefficient) = 0.24
Mass1250 g (2.8 lb)
Series5500
Fuse rating500 mA
(fuse rating on 5500 control unit)
Dimensionssee dimensions
Material
Housing: anodized aluminum
3/8"" compression fittings: 316 stainless steel
Pressure ports: 3/8"" NPTF
Bulkhead fitting: 316 stainless steel
Mounting bolts: 1/4 - 20, 316 stainless steel
Sealing washers: UL recognized type 4X
Pressure requirement1.4 bar (20 psi) to 8.2 bar (120 psi)
Operating modeautomatic purging
Protective gas supplyinstrument grade air or inert gas
Ambient temperature-20 ... 50 В°C (-4 ... 122 В°F)
Hazardous environmentgas or dust
Rated power24 V DC: 5.6 W
Voltage tolerance: +/- 10 %
CSA approvalClass I Division 2, Group A-D
Class II Division 2, Group F+G

Comments

No comments yet

Write a comment