Pepperl+Fuchs 6500-01-*-PNO-LNO
6500 Control Unit

Pepperl+Fuchs 6500-01-*-PNO-LNO
  • Automatic purge and pressurization system for most applications
  • User-friendly, easy programming
  • LCD screen for operation status and LED's for quick visual identification of system
  • HART communication through RS485 with PACTware and device app's through Bluetooth
  • Maximum enclosure size 12.75 cubic meters
  • Compact design with panel mounts or direct mounts available
  • Universal power 20 to 30 VDC / 100 to 250 VAC. 50 to 60 HZ
  • Pressure, temperature, dilution control and monitoring
  • Up to SIL 2 acc. to IEC 61508
Item Number: 6500-01-*-PNO-LNO
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments

Continuous (Dilution) vent series: EPV-6500-*-07, 08
Readout on display is from 17 to 226 l/min (0.6 to 8 scfm) continuous reading.
Maximum reading depending on type of vent and supply pressure.
See data sheet for EPV-6500 series vent.
Degree of protectionIP66
Output IIIDigital valve
When used with the 6500-MAN-DV-01, intrinsically safe
Internal resistance 280 andOmega;
IECEx approvalIECEx UL / DEMKO 15.0147X

Relative humidity5 ... 85 %, non-condensing
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Safety Integrity Level (SIL)SIL 2
Massapprox. 5 kg (11.0 lbs)
Hazardous environmentgas, dust, gas and dust
Impact resistance30 g, 11 ms, all axes
Display elements2x20 LCD for configuration, monitoring, and status of the 65000 system with back light and contrast selection. Capacitive touch buttons
Input II(1) 2-wire, PT100 RTD
Pressure requirementFor 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120psig) regulated
For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig) regulated
Note: max. pressure will depend on the vent model used. regulated
ConnectionEPCU: Terminal blocks and grounding screw
UIC: 4-pin conncector and cable (provided), for the 6500-01-PM02, cable length is 5 meters
Input type: intrinsically safe
Operating modeuser programmable
Output IVProportional valve
When used with the 6500-MAN-PV-01, intrinsically safe
Current: 4 to 20 mA
Max. load: 300 andOmega;
Connection typeSee mounting in 6500 manual and cable gland requirements
Input IVoltage free contact or namur proximity sensor
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
CommunicationHART via RS485 (PACTware available)
Rated voltage100 ... 240 V AC, 48 ... 62 Hz / 0.2 A
20 ... 30 V DC
Cable glandCable gland requirement: cable glands are not included. Customer can supply there own approved glands or use one of the 6500-CBLG-... cable gland kits.
I.S.cable glands: requires (5) M12 approved cable glands
Power cable glands: requires (2) m20 and (2) M12 approved cable glands
Number of volume exchanges5 to 19
MaterialUIC display: Makrolon FI cover and A380 Aluminum anodized casing
Housing: 316L stainless steel
Hardware: 316L stainless steel
EU-Type Examination CertificateATEX UL / DEMKO 15 ATEX 1622X
Output IAUX
Dimensions6500-01-EXT1: 150 x 150 x 145 mm (5.9"" x 5.9"" x 5.7"")
6500-01-PM01: 150 x 150 x 185 mm (5.9"" x 5.9"" x 7.3"")
6500-01-PM02: EPCU: 150 x 150 x 145 mm (5.9"" x 5.9"" x 5.7""), UIC: 150 x 150 x 45 mm (5.9"" x 5.9"" x 1.8"")
LED indicatorSafe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault
Key: green - a button on the capacitive touch display has been activated. Momentary indication
Valve flowsStandard vent series: EPV-6500-*-01, 03, 05
Readout on display is from 56 to 850 l/min (2 to 30 scfm) in increments of 28l/min (1 scfm).
Minimum and maximum reading depending on type of vent and supply pressure.
See data sheet for EPV-6500 series vent.
Series6500
Protective gas supplyinstrument grade air or inert gas
Storage temperature-40 ... 70 В°C (-40 ... 158 В°F)
Safe pressureGas: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Dust: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Gas+Dust: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Output IIEnclosure
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes

Comments

No comments yet

Write a comment