Pepperl+Fuchs F2-SP-IC*
Fieldbus Segment Protector
- 4 ... 10 outputs Ex ic (FISCO or Entity)
- Advanced fault isolation at the spur
- Segment Protector in Zone 2
- Instruments in Zone 2 or Zone 1
- For FOUNDATION Fieldbus H1 and PROFIBUS PA
- Advanced Diagnostics at the spur
- Power, Com, Terminator, Diagnostics, and Error LEDs
Item Number:
F2-SP-IC*
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Mass | max 2.6 kg , depending on model |
Ambient temperature | see table 2 |
LED SPURS | red: 2 Hz flashing in short-circuit condition |
Mounting | panel mounting |
FOUNDATION Fieldbus | FF-846 |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
Design / Mounting | Outside installation |
Vibration resistance | 5 g , 10 ... 150 Hz |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Cable gland | see table 2 |
Degree of protection | IP66 |
Climatic conditions | IEC 60721 |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
EU-Type Examination Certificate | TГњV 13 ATEX 107689 X |
IECEx approval | IECEx TUN 13.0004X |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
LED PWR/TERM | green: Fieldbus voltage > 10 V and fieldbus terminator is activated |
Shock resistance | 15 g , 11 ms |
Marine approval | DNV A-14038 |
Connection type | removable screw terminal , removable spring terminal , screw terminal |
Jumper 2 | configuration of grounding option for trunk and cable screen/shield |
Core cross-section | max. 2.5 mm2 /AWG 12-24 |
Relative humidity | < 95 % non-condensing |
Dimensions | see table 2 |
Storage temperature | -40 ... 85 В°C (-40 ... 185 В°F) |
Cable diameter | see table 3 |
Vibration resistance | EN 60068-2-6 |
Housing | see figure 1 |
Jumper 1 | configuration of short-circuit current/rated current |
Voltage drop main cable/outputs | max. 1.2 V |
Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V |
Shock resistance | EN 60068-2-27 |
Self current consumption | see table ""Technical data depending on model"" |
Voltage drop trunk In/Out | 0 V |
Terminating resistor | selectable via Jumper 100 andOmega; +/- 10 % |
Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
People also buy
Comments
No comments yet