Pepperl+Fuchs FB4205C2
HART Output Isolator with Shutdown Input

Pepperl+Fuchs FB4205C2
We ship to United States of America!
  • 4-channel
  • Outputs Ex ia
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Analog output module for 0/4 mA ... 20 mA
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD): one LED per channel
  • Permanently self-monitoring
  • Output with bus-independent safety shutdown
Item Number: FB4205C2
1190.30
-
+
Total price: 1190.30
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

HART secondary variableyes

Refresh time100 ms
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
HART secondary variableno
Massapprox. 750 g
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
HART communicationyes
ATEX approvalBVS 12 ATEX E 015 X
Shock resistanceEN 60068-2-27:2009
Interfacemanufacturer-specific bus to standard com unit
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Degree of protectionIEC 60529:2000
Power dissipation2.15 W
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Connectionbackplane bus
Load750 andOmega; max.
Environmental testEN 60068-2-14:2009
Vibration resistanceEN 60068-2-6:2008
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Relative humidity95 % non-condensing
Codingoptional mechanical coding via front socket
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power consumption3.3 W
Damaging gasEN 60068-2-42:2003
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
EAC approvalRussia: RU C-IT.MIII06.B.00129
Occupied slots2
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
EU-Type Examination CertificateBVS 12 ATEX E 015 X
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionbackplane bus
Number of channels4
Electromagnetic compatibilityNE 21:2007
Relative humidityEN 60068-2-78:2001
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Current0 ... 25 mA short-circuit protected
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
INMETROBrazil: TГњV 14.1595X
HART communicationyes
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit)
Connectionterminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-

Buy Pepperl+Fuchs FB4205C2 with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com is an online electrical parts store. Here you can find a wide range of electrical and automation equipment. We ship to any country as quickly as possible. You will get your order fast and with good prices. Our team is always willing to help and tries to find the best solution for you. Don’t hesitate to become one of our customers, you will not regret it!

Comments

No comments yet

Write a comment