Pepperl+Fuchs FB8206H0630
EasyCom Com Unit for PROFIBUS DP/DP-V1

Pepperl+Fuchs FB8206H0630
We ship to United States of America!
  • Interface between the I/O modules and the PCS/PLC
  • Com unit for 80 analog or 184 digital channels
  • Communication via PROFIBUS DP
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • HART communication via PROFIBUS DP V1 or service bus
  • Configuration via GSD parameters from the control system
  • Non-volatile memory for configuration and parameter settings
  • Self configuration in redundant systems
  • Permanently self-monitoring
  • Outputs drive to safe state in case of failures
Item Number: FB8206H0630
Price on Request
-
+
Total price: € 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
GSE fileCGV61711.gsd/gse
Cyclic process data240 bytes input and (simultaneously) 240 bytes output
Massapprox. 750 g
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
LED indicationLED green (power supply): On = operating, fast flash = cold start
LED red (collective alarm): On = internal fault, flashing = no PROFIBUS connection
LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation
Connectionvia backplane
Connectionbackplane bus
Power dissipation1.8 W
Storage temperature-25 ... 85 ?Β°C (-13 ... 185 ?Β°F)
Number of stations per bus segmentmax. 31 (RS-485 standard)
Bus lengthmax. 1000 m (FOL, 1.5 MBaud),
max. 1000 m (copper cable, 187.5 kBd),
max. 200 m (copper cable, 1.5 MBd)
EU-type examination certificatePTB 97 ATEX 1074 U
Number of stations per bus linemax. 125 (PROFIBUS), max. 119 (service bus)
Rated voltage5 V DC , only in connection with the power supplies FB92**
PROFIBUS address0 ... 126
(factory standard setting: 126)
Environmental testEN 60068-2-14
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ?Β± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ?Β± 1 mm/0.7 g; 90 minutes at each resonance
HART communicationvia PROFIBUS or service bus
Supported I/O modulesall FB remote I/O modules
Fieldbus typePROFIBUS DP/DP-V1
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Shock resistanceEN 60068-2-27
Addressingvia configuration software
Relative humidityEN 60068-2-56
Fieldbus standardIEC 61158-2
Electromagnetic compatibilityNE 21
Connectionbackplane bus
Vibration resistanceEN 60068-2-6
Number of repeaters between Master and Slavemax. 3
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Redundancyvia front connector
Relative humidity95 % non-condensing
Ambient temperature-20 ... 60 ?Β°C (-4 ... 140 ?Β°F)
System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Power consumption1.8 W
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
EAC approvalRussia: RU C-IT.MIII06.B.00129
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Degree of protectionIEC 60529
Damaging gasEN 60068-2-42

Buy Pepperl+Fuchs FB8206H0630 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. offers electrical products online. We offer a comprehensive range of reliable and high-efficiency products. Express delivery is available to all our clients. We offer only original products from well-known manufacturers. If you need the products very urgently, we will do our best to provide you with the fastest delivery. We have a lot of positive feedback from our clients and partners, we are recommended!

Comments

No comments yet