Pepperl+Fuchs FB8207*
Com Unit for MODBUS RTU
- Interface between the I/O modules and the PCS/PLC
- Com unit for 80 analog or 184 digital channels
- Communication via MODBUS RTU
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
- HART communication via service bus
- Configuration via FDT 1.2 DTM
- Non-volatile memory for configuration and parameter settings
- Self configuration in redundant systems
- Permanently self-monitoring
- Outputs drive to safe state in case of failures
Item Number:
FB8207*
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Redundancy | via front connector |
Number of repeaters between Master and Slave | max. 3 |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Service bus address | max. 119 , redundancy address = base + 128 (automatic) |
Connection | backplane bus |
LED indicator | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no Modbus RTU connection LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation |
ATEX approval | PTB 97 ATEX 1075 |
Relative humidity | 95 % non-condensing |
Addressing | via configuration software |
HART communication | via service bus |
Degree of protection | IEC 60529 |
EU-Type Examination Certificate | PTB 97 ATEX 1074 U |
Number of channels per station | max. 80 analog, max. 184 digital (standard configuration) |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
FOL (fiber optic link) | additional hardware required |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Mass | approx. 750 g |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** |
Fieldbus type | MODBUS RTU |
Connection | backplane bus |
Number of stations per bus line | max. 245 (MODBUS), max. 119 (service bus) |
Number of stations per bus segment | max. 31 (RS-485 standard) |
Power consumption | 2 W |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Supported I/O modules | all FB remote I/O modules |
Electromagnetic compatibility | NE 21 |
MODBUS address | standard compliant (factory standard setting: 126) |
Bus length | max. 1200 m (FOL, 38.4 kBd), max. 1200 m (copper cable, 38.4 kBd) |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance |
Connection | via backplane |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |