Pepperl+Fuchs FB9210-PB0-0-0-0-0-F
  • Standard enclosure for FB-System
  • Max. 5 slots for I/O modules
  • For FOUNDATION Fieldbus H1
  • Impact resistance enclosure, IP66/NEMA 4X
  • Packaged certified solution
  • Installation in Zone 1
Item Number: FB9210-PB0-0-0-0-0-F
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
I/O modules (single width)-
Rated voltage24 V DC/115 V AC/230 V AC , depends on power supply
EU-Type Examination CertificatePTB 97 ATEX 1075 X
Bus coupler1
Massapprox. 10 kg , without modules
Mountingthru-holes ГPEPPERL+FUCHS/Explosion Protection/Remote IO Systems;FB9215B2;0.00;pepperl-fuchs-fb9215b2;0;0;Pepperl+Fuchs;;;;;;Power supply;;
  • Multi range power supply 90 ... 253 V AC
  • Suitable for the supply of 24 I/O modules and 1 bus coupler
  • Use two power supplies for redundancy
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
;Voltage5.4 V DC +/- 5% ,
12 V DC +/- 3%
Degree of protectionIEC 60529:2000
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Inrush current (< 2 ms)30 A max. (115 V AC)
50 A max. (230 V AC)
Maximum safe voltage Um253 V AC
Power dissipationapprox. 18 % of power consumption
Electromagnetic compatibilityNE 21:2007
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
LED indicatorLED green: OFF in case of loss of main power or internal voltages (12 V, 5.4 V)
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Vibration resistancefrequency range 10 ... 150 Hz