Pepperl+Fuchs HD2-FBPS-1.500
Fieldbus Power Hub, Power Supply Module

Pepperl+Fuchs HD2-FBPS-1.500
  • Output: 28 ... 30 V/500 mA
  • High-power trunk for high device count and long cable lengths
  • With galvanic isolation
  • Installation in Zone 2/Class I, Div. 2
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • High efficiency, low heat dissipation for high packing density
  • Hot swappable in redundant configuration
  • Module exchange without tools during operation
Item Number: HD2-FBPS-1.500
1191.35
-
+
Total price: 1191.35
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Relative humidity< 95 % non-condensing

LED ERRred flashing: short-circuit or undervoltage at output
Rated current500 ... 10 mA
Mountingmotherboard mounting
Marine approvalpending
Connection typemotherboard specific
Electromagnetic compatibilityNE 21:2011
Massapprox. 150 g
Core cross-sectionmotherboard specific
Rated current910 ... 490 mA
Degree of protectionIEC 60529
Housing height106 mm
LED PWRgreen if Uout > 28 V
Fieldbus segment/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 250 V AC
Short-circuit current550 mA
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Vibration resistanceEN 60068-2-6
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Rated voltage19.2 ... 35 V DC
Degree of protectionIP20
Pollution degreemax. 2, according to IEC 60664
Fieldbus standardIEC 61158-2
Housing materialPolycarbonate
Housing depth128 mm
Housing width18 mm
Design / MountingMotherboard based
Rated voltage28 ... 30 V
CertificateTГњV 04 ATEX 2500 X
Vibration resistance1 g , 10 ... 150 Hz
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Shock resistanceEN 60068-2-27
Shock resistance15 g 11 ms
Power dissipationtyp. 1.8 W
Ambient temperature-40 ... 70 В°C (-40 ... 158 В°F)

Comments