Pepperl+Fuchs HD2-GTR-4PA
PROFIBUS Power Hub, Gateway Module

Pepperl+Fuchs HD2-GTR-4PA
  • PROFIBUS DP V1 / For 4 segments PA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • Optional redundant configuration
  • Installation in Zone 2/Class I, Div. 2
  • Up to 12 Mbit/s, auto adapting
  • For redundant and non-redundant masters
  • Supports Flying Redundancy (FR)
  • Cyclic/acyclic data exchange
Item Number: HD2-GTR-4PA
3384.56
-
+
Total price: 3384.56
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Fieldbus standardIEC 61158-2

Ambient temperature-40 ... 60 В°C (-40 ... 140 В°F)
Vibration resistance1 g , 10 ... 150 Hz
Rated current160 ... 90 mA
CH/PROFIBUS DPfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
PROFIBUS DP/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Relative humidity< 95 % non-condensing
Galvanic isolationIEC 62103
LED Red.yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available
LED Seg 1...4red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error
Design / MountingMotherboard based
Electromagnetic compatibilityNE 21:2011
Power dissipation3 W
CH/CHfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Housing height106 mm
Housing width40 mm
Housing depth128 mm
Shock resistance15 g 11 ms
Marine approvalDNV A-14038
Vibration resistanceEN 60068-2-6
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
LED DP/ERRred 2 Hz flashing: DP error ; red: Hardware error
Mass250 g
Degree of protectionIEC 60529
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Housing materialPolycarbonate
Mountingmotherboard mounting , mounting in any orientation
Shock resistanceEN 60068-2-27
All circuits/FEfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Degree of protectionIP20
Rated voltage19.2 ... 35 V DC
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
LED PWRgreen: Power on
Pollution degreemax. 2, according to IEC 60664
CertificateTГњV 04 ATEX 2500 X

Comments

No comments yet

Write a comment