Pepperl+Fuchs HiC2027
SMART Transmitter Power Supply

Pepperl+Fuchs HiC2027
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input for 2-wire SMART transmitters and current sources
  • Signal splitter (1 input and 2 outputs)
  • Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V
  • Up to SIL 2 acc. to IEC 61508
Item Number: HiC2027
550.00
-
+
Total price: 550.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Power dissipationapprox. 1.4 W at 20 mA transfer current, 250 andOmega; in both outputs.

Safety Integrity Level (SIL)SIL 2
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
CertificateBASEEFA 13 ATEX 0076 X
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Power consumption2 W
Rise time/fall time2 ms
Voltage dropSL2: 1a(+), 1b(-), 7a(-): 6.1 V at 20 mA
Connection sidefield side
Labelingspace for labeling at the front
Control elementsDIP-switch
Signal typeAnalog input
Codingpin 2 and 3 trimmed
For further information see system description.
Configurationvia DIP switches
ConnectionSL2: 5a(+), 5b(-): sink
SL2: 1a(+), 1b(-), 7a(-): source
Rated voltage18 ... 30 V DC bus powered via Termination Board
Equipmentterminals 1a, 1b, 7a
Settling time6 ms
Input resistanceSL2: 5a(+), 5b(-): max. 500 andOmega;
(250 andOmega; load)
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Available voltageSL2: 5a(+), 5b(-): 16 V at 20 mA , 18.5 V at 4 mA
ConnectionSL1: 8a(+), 7a(-), channel 1: source and sink
SL1: 10a(+), 9a(-), channel 2: source and sink
Massapprox. 100 g
Input signal0/4 ... 20 mA
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Degree of protectionIP20
Equipmentterminals 5a, 5b
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Loadchannel 1: 0 ... 500 andOmega; (20 mA)/> 1 MandOmega; (5 V)
channel 2: 0 ... 500 andOmega; (20 mA)/> 1 MandOmega; (5 V)
Connection sidecontrol side
Short-circuit currentSL2: 5a(+), 5b(-): 25 mA
Degree of protectionIEC 60529:2001
Ripplemax. 50 andmicro;A rms
Output signal0/4 ... 20 mA or 0/1 ... 5 V
Display elementsLED
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB)
Ripplewithin the supply tolerance
NoteBoth output loads must be connected to ensure complete and correct operation within the technical specification.
DeviationIout < 20 andmicro;A (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 В°C (68 В°F), 0/4 ... 20 mA, 0/1 ... 5 V
Protection against electrical shockUL 61010-1:2012
EU-Type Examination CertificateBASEEFA 13 ATEX 0075 X
IECEx approvalIECEx BAS 13.0042X

Comments

No comments yet

Write a comment