Pepperl+Fuchs HiC2031
SMART Current Driver
- 1-channel isolated barrier
- 24 V DC supply (bus powered)
- Current output up to 650 Omega- load
- Low power dissipation
- Up to SIL 2 acc. to IEC 61508
Item Number:
HiC2031
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Degree of protection | IP20 |
Connection side | field side |
Deviation | at 20 В°C (68 В°F), 0/4 ... 20 mA В± 0.1 % incl. non-linearity and hysteresis |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Configuration | via DIP switches |
Load | 0 ... 650 andOmega; |
Input signal | 4 ... 20 mA limited to approx. 30 mA |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Ripple | 10 % |
Rated current | 30 mA |
Power dissipation | 600 mW |
Input resistance | > 100 kandOmega;, with field wiring open |
Signal type | Analog output |
Degree of protection | IEC 60529:2001 |
Safety Integrity Level (SIL) | SIL 2 |
Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA |
Rise time | 10 to 90 % 100 ms |
Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Labeling | space for labeling at the front |
Ripple | 20 mV rms |
EU-Type Examination Certificate | CESI 06 ATEX 017 |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Connection | SL1: 8a(+), 7a(-) |
Control elements | DIP-switch |
Current | 4 ... 20 mA |
Input/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Voltage | 13 V at 20 mA |
Mounting | on Termination Board |
Connection side | control side |
Coding | pin 1 and 3 trimmed For further information see system description. |
Equipment | SL2: 5a(+), 5b(-) |
Power consumption | 700 mW |
Mass | approx. 100 g |
Display elements | LED |
Certificate | KIWA 15 ATEX 0035 X |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Input voltage | depending on switch configuration open loop voltage of the control system < 23 V open loop voltage of the control system < 27 V |
Connection | SL2: 5a(+), 5b(-) |