Pepperl+Fuchs HiC2441
SMART Universal Barrier

Pepperl+Fuchs HiC2441
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Analog input, digital input,
    analog output, digital output
  • No configuration required, device is self-adapting
  • HART transparency
  • Low power dissipation
  • 3-way isolation
  • Up to SIL 2 acc. to IEC 61508
Item Number: HiC2441
423.96
-
+
Total price: 423.96
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Ambient temperature-40 ... 70 В°C (-40 ... 158 В°F)
Observe the temperature range limited by derating, see section derating.
Field circuitSL2: 5a(+), 5b(-)
Signal typeUniversal
Frequency rangeHART: bandwidth by 0.5 Vpp signal and/or 1 mApp signal 950 ... 2500 Hz (analog input, analog output)
InputEN 60947-5-6:2000
Ripple20 mV rms
Power consumption 700 mW
Voltage12 ... 30 V
UL approvalE106378
Protection against electrical shockIEC 61010-1:2010
EquipmentSL2: 5a(+), 1a(-)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Deviationat 20 В°C (68 В°F)
В±20 andmicro;A incl. linearity, hysteresis and supply fluctuations at 4 ... 20 mA (analog input, analog output)
В±60 andmicro;A incl. linearity, hysteresis and supply fluctuations at 0 ... 45 mA (digital output)
Signal0.1 ... 9 mA
Supply voltagemin. 16 V at 20 mA (2-wire SMART transmitter)
Control circuitSL1: 8a(+), 7a(-)
Switching frequency 500 Hz with 50 % duty cycle (digital input, NAMUR sensor)
5 Hz (digital input, dry contact)
20 Hz (digital output)
Field circuitSL2: 5a(+), 5b(-)
Voltage1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
EquipmentSL2: 5a(+), 1b(-)
Suitable field devicesI/P converters (positioner), on-site-displays
Load0 ... 650 andOmega;
Line fault detection> 100 kandOmega; at max. 30 V, with field wiring open
Codingpin 1 and 4 trimmed
For further information see system description.
Suitable field devicesNAMUR sensors according to IEC/EN 60947-5-6, dry contacts
Rated current 30 mA
Drive capability12 V / 40 mA at 300 andOmega; load
CertificateTГњV 14 ATEX 153523 X
Signal0/4 ... 20 mA , sink mode , working voltage 15 ... 30 V
Ripple 10 %
Current limit45 mA
Suitable field devicessolenoid valves, acoustic or visual alarms
Signal0/4 ... 20 mA
Safety Integrity Level (SIL)SIL 2
Voltage 13 V at 20 mA
Mountingon Termination Board
EU-Type Examination CertificateTГњV 14 ATEX 153522 X
Voltage dropapprox. 4 V (current source)
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
EquipmentSL2: 5a(+), 5b(-)
Power dissipation1.1 W at 24 V, 300 andOmega; load (digital output)
Field circuitSL2: 5a(+), 1a(-) (NAMUR sensor)
SL2: 5a(+), 5b(-) (dry contact)
Signal0/4 ... 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Settling time 20 ms (analog input, analog output)
1 ms (digital input, NAMUR sensor)
Suitable field devices2-wire SMART transmitters, current sources
Control circuitSL1: 8a(+), 7a(-)
Voltage13 ... 30 V
Electromagnetic compatibilityNE 21:2011
Signal0.1 ... 9 mA , sink mode
Open loop voltageapprox. 22 V
Field circuitSL2: 5a(+), 5b(-) (2-wire SMART transmitter)
SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source)
Open loop voltageapprox. 10 V DC , 1 kandOmega; series resistance
Degree of protectionIP20
Rated voltage19 ... 30 V DC via Termination Board
Degree of protectionIEC 60529:2001
Voltage15 ... 30 V
Relative humidity95 % non-condensing
Ripple20 mV rms
Massapprox. 100 g
Control circuitSL1: 8a(+), 7a(-)
Control circuitSL1: 8a(+), 7a(-)
Control/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Internal resistormin. 240 andOmega;
Signal0/4 ... 20 mA
Current1-signal: 0 ... 45 mA, depending on the output load
0-signal: < 0.1 mA, independent of the output load
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)