Minimum switch current2 mA / 24 V DC
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Signal typeDigital Input
Rated current 30 mA
Ripple 10 %
Massapprox. 100 g
Contact loading50 V DC / 0.5 A
CertificatePF 08 CERT 1047 X
Degree of protectionIEC 60529:2001
Switching frequency 10 Hz
Energized/De-energized delay 20 ms / 20 ms
Codingpin 1 and 2 trimmed
For further information see system description.
Galvanic isolationEN 50178:1997
ConnectionSL1: 6b
Labelingspace for labeling at the front
ConnectionSL1: 8a, 7a; 10a, 9a
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
ConnectionSL2: 5a(+), 5b(-)
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Display elementsLEDs
Mountingon Termination Board
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output IIsignal or error message ; relay
Electromagnetic compatibilityNE 21:2006
For further information see system description.
InputEN 60947-5-6:2000
Output typeopen collector transistor (internal fault bus)
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Output Isignal ; relay
Mechanical life107 switching cycles
Safety Integrity Level (SIL)SIL 2
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Power consumption 500 mW
Power dissipation 500 mW
Degree of protectionIP20
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
EU-Type Examination CertificateBASEEFA 06 ATEX 0093 X
Control elementsDIP-switch
Configurationvia DIP switches
Rated voltage19 ... 30 V DC bus powered via Termination Board
Connection sidecontrol side
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Connection sidefield side
IECEx approvalIECEx BAS 06.0026X
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Line fault detectionbreakage I 0.1 mA , short-circuit I 6.5 mA