Pepperl+Fuchs HiC2822
Switch Amplifier

Pepperl+Fuchs HiC2822
We ship to United States of America!
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Dry contact or NAMUR inputs
  • 2 relay contact outputs
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508
Item Number: HiC2822
268.35
-
+
Total price: 268.35
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
CertificatePF 08 CERT 1047 X
ConnectionSL1: 8a, 7a; 10a, 9a
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Massapprox. 100 g
Degree of protectionIEC 60529:2001
Energized/De-energized delay 20 ms / 20 ms
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Display elementsLEDs
Power dissipation 600 mW
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Connection sidefield side
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Contact loading50 V DC / 0.5 A
Line fault detectionbreakage I 0.1 mA , short-circuit I 6.5 mA
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Rated current 30 mA
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mechanical life107 switching cycles
ConnectionSL1: 6b
Codingpin 1 and 2 trimmed
For further information see system description.
IECEx approvalIECEx BAS 06.0026X
Galvanic isolationEN 50178:1997
Pulse/Pause ratiomin. 20 ms / min. 20 ms
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Output typeopen collector transistor (internal fault bus)
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Power consumption 600 mW
Control elementsDIP-switch
Minimum switch current2 mA / 24 V DC
Safety Integrity Level (SIL)SIL 2
Output Isignal ; relay
InputEN 60947-5-6:2000
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Labelingspace for labeling at the front
Connection sidecontrol side
Output IIsignal ; relay
Switching frequency 10 Hz
Ripple 10 %
Signal typeDigital Input
Degree of protectionIP20
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Mountingon Termination Board
Rated voltage19 ... 30 V DC bus powered via Termination Board
Configurationvia DIP switches
EU-Type Examination CertificateBASEEFA 06 ATEX 0093 X

Buy Pepperl+Fuchs HiC2822 with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com is an electrical online store. We offer a full range of industrial automation equipment. Your order can be shipped with super fast delivery! Discover the best price in our web catalog. The offer submission date is always optimal for you. Safety, simplicity, and support during every stage.

Comments

No comments yet

Write a comment