Pepperl+Fuchs HiC2873
Solenoid Driver

Pepperl+Fuchs HiC2873
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (bus or loop powered)
  • Output 40 mA at 12 V DC, 55 mA current limit
  • Contact or logic control input
  • Entity parameter Io/Isc = 110 mA
  • Line fault detection (LFD)
  • Test pulse immunity
  • Up to SIL 2 acc. to IEC 61508 (bus powered)
  • Up to SIL 3 acc. to IEC 61508 (loop powered)
Item Number: HiC2873
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Signal level1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kandOmega; pull-up)
0-signal: 0...5 V DC or contact open
Output/power supply, inputs, and collective errorsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Massapprox. 100 g
Labelingspace for labeling at the front
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Control inputexternal switch (dry contact or open collector) non isolated or logic signal input fully floating
Connection sidefield side
Codingpin 1 and 4 trimmed
For further information see system description.
Configurationvia DIP switches
Input current62 mA at 24 V, 300 andOmega; load
ConnectionSL2: 5a(+), 5b(-)
Display elementsLEDs
Power dissipation1 W at 24 V, 300 andOmega; load
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Current 40 mA
Power dissipation1 W at 24 V, 300 andOmega; load for loop powered
Safety Integrity Level (SIL)SIL 3
Open loop voltageapprox. 22.5 V
ConnectionSL1: 6b
Internal resistorapprox. 240 andOmega;
ConnectionSL1: 8a(+), 7a(-) loop powered
SL1: 10a(+), 9a(-) bus powered
Switching frequency- bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz
- loop powered: max. 10 Hz
Rated voltage20.4 ... 30 V DC loop powered
20.4 ... 30 V DC bus powered via Termination Board
Current limit55 mA
Voltage 12 V
Electromagnetic compatibilityNE 21:2006
For further information see system description.
EU-Type Examination CertificateCESI 10 ATEX 046
Fault levellead short-circuit detection at < 25 andOmega;
lead breakage detection at > 100 kandOmega; typical
Output typeopen collector transistor (internal fault bus)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal typeDigital Output
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
CertificateKIWA 15 ATEX 0036 X
Connection sidecontrol side
Degree of protectionIP20
Inrush current0.2 A , 15 ms loop powered
Loadnominal 0.1 ... 5 kandOmega;
Fault current4 mA pulsing (20 ms ON, 200 ms OFF)
Control elementsDIP-switch
Mountingon Termination Board
Energized/De-energized delay- bus powered: filter OFF: 1 ms, filter ON: 10 ms
- loop powered: switch-on 50 ms, switch-off 6 ms (300 andOmega; load)
Degree of protectionIEC 60529:2001

Buy Pepperl+Fuchs HiC2873 with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com offers industrial control components. A variety of product types and sizes is available in our web catalog. All your ordered products can be sent in one delivery. We offer a price match guarantee. You can pay for multiple offers with one payment. With each day we gain more and more experience and that's why we are able to satisfy your needs for spare parts.

Comments

No comments yet

Write a comment