Pepperl+Fuchs HiC2873Y1
Solenoid Driver

Pepperl+Fuchs HiC2873Y1
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Output 40 mA at 12 V DC, 55 mA current limit
  • Contact or logic control input
  • Entity parameter Io/Isc = 110 mA
  • Line fault detection (LFD)
  • Test pulse immunity
  • Up to SIL 2 acc. to IEC 61508 (bus powered)
Item Number: HiC2873Y1
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Connection sidecontrol side
Safety Integrity Level (SIL)SIL 2
Mountingon Termination Board
Open loop voltageapprox. 22.5 V
Massapprox. 100 g
ConnectionSL1: 6b
Signal level1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kandOmega; pull-up)
0-signal: 0...5 V DC or contact open
Degree of protectionIEC 60529:2001
Voltage 12 V
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Current 40 mA
Internal resistorapprox. 240 andOmega;
Fault levellead short-circuit detection at < 25 andOmega;
lead breakage detection at > 100 kandOmega; typical
Degree of protectionIP20
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Output typeopen collector transistor (internal fault bus)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Display elementsLEDs
Current limit55 mA
EU-Type Examination CertificateCESI 10 ATEX 046
Labelingspace for labeling at the front
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Power dissipation1 W at 24 V, 300 andOmega; load
Loadnominal 0.1 ... 5 kandOmega;
Input current62 mA at 24 V, 300 andOmega; load
Control elementsDIP-switch
Fault current4 mA pulsing (20 ms ON, 200 ms OFF)
Configurationvia DIP switches
Codingpin 1 and 4 trimmed
For further information see system description.
Connection sidefield side
CertificateKIWA 15 ATEX 0036 X
Signal typeDigital Output
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Control inputexternal switch (dry contact or open collector) non isolated or logic signal input fully floating
ConnectionSL2: 5a(+), 5b(-)
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
ConnectionSL1: 8a(+), 7a(-)
Output/power supply, inputs, and collective errorsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V

Buy Pepperl+Fuchs HiC2873Y1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. offers industrial control products. Our online catalog offers a wide selection of product types and sizes. We consolidate all your goods and send them in one delivery. Become our client and get unbelievable prices for all automation equipment. Quotes are always sent quickly after your request. During the past years, we managed to develop enough to satisfy the requirements of our customers.