Pepperl+Fuchs HiC2873Y1
Solenoid Driver
- 1-channel isolated barrier
- 24 V DC supply (bus powered)
- Output 40 mA at 12 V DC, 55 mA current limit
- Contact or logic control input
- Entity parameter Io/Isc = 110 mA
- Line fault detection (LFD)
- Test pulse immunity
- Up to SIL 2 acc. to IEC 61508 (bus powered)
- Overview
- Comments
Connection side | control side |
Safety Integrity Level (SIL) | SIL 2 |
Mounting | on Termination Board |
Open loop voltage | approx. 22.5 V |
Mass | approx. 100 g |
Connection | SL1: 6b |
Signal level | 1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kandOmega; pull-up) 0-signal: 0...5 V DC or contact open |
Degree of protection | IEC 60529:2001 |
Voltage | 12 V |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Current | 40 mA |
Internal resistor | approx. 240 andOmega; |
Fault level | lead short-circuit detection at < 25 andOmega; lead breakage detection at > 100 kandOmega; typical |
Degree of protection | IP20 |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Output type | open collector transistor (internal fault bus) |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Display elements | LEDs |
Current limit | 55 mA |
EU-Type Examination Certificate | CESI 10 ATEX 046 |
Labeling | space for labeling at the front |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Power dissipation | 1 W at 24 V, 300 andOmega; load |
Load | nominal 0.1 ... 5 kandOmega; |
Input current | 62 mA at 24 V, 300 andOmega; load |
Control elements | DIP-switch |
Fault current | 4 mA pulsing (20 ms ON, 200 ms OFF) |
Configuration | via DIP switches |
Coding | pin 1 and 4 trimmed For further information see system description. |
Connection side | field side |
Certificate | KIWA 15 ATEX 0036 X |
Signal type | Digital Output |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Control input | external switch (dry contact or open collector) non isolated or logic signal input fully floating |
Connection | SL2: 5a(+), 5b(-) |
Connection | SL1: 1a, 1b(-); 2a, 2b(+) |
Connection | SL1: 8a(+), 7a(-) |
Output/power supply, inputs, and collective error | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
People also buy
Comments
No comments yet