Pepperl+Fuchs HiC5861

Relay Module
Pepperl+Fuchs HiC5861
Price on Request
One click request
Mountingon Termination Board
Test pulse lengthmax. 4 ms from DO card
ConnectionInput SL1: 8a(+), 7a(-) ; test input SL1: 3a(-), 3b(+), 4a(+), 4b(+)
Connection sidefield side
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: 36 mA (minimum load current DO card)
Contact loading30 V DC/1 A resistive load
Switching frequency< 3 Hz
Safety Integrity Level (SIL)SIL 3
Fuse rating1.5 A
Energized/De-energized delay150 ms / 150 ms
Massapprox. 100 g
Pulse/Pause ratio150 ms / 150 ms
Mechanical life2 x 107 switching cycles
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Observe the temperature range limited by derating, see section derating.
Power consumption< 1.3 W
Codingno pin trimmed
For further information see system description.
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff
ConnectionSL2: 5a, 5b
Test inputsee Functional Safety Manual
Degree of protectionIEC 60529:2013
Power dissipation< 1.3 W
UL approvalE106378
Performance level (PL)PL e
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Connectionloop powered
Rated voltage19 ... 30 V DC loop powered
CertificatePF 17 CERT 4192 X
Labelingspace for labeling at the front
Minimum switch current10 mA / 24 V DC
Display elementsLEDs
Degree of protectionIP20
Rated voltage19 ... 27.6 V loop powered
Signal level0-signal: -5 ... 5 V
1-signal: 19 ... 27.6 V
Signal typeDigital Output
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008
Connection sidecontrol side
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff
in international format without spaces