Pepperl+Fuchs HiCTB16-HIM-RAC-SP-AO1601

Termination Board
Pepperl+Fuchs HiCTB16-HIM-RAC-SP-AO1601
612.18
One click request

IECEx approvalIECEx CES 06.0003

Core cross-section0.25 ... 1.5 mm2 (24 ... 16 AWG)
ConnectionXG2: terminals 5, 6
ConnectionXG2: terminals 1, 3 (+); 2, 4 (-)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Reverse polarity protectionyes
Ripple≤ 10 %
Fusing4 A , in each case for 16 modules
Display elementsLED PWR1 (Termination Board power supply), green LED
LED PWR2 (Termination Board power supply), green LED
LED FAULT (fault indication), red LED
- LED lits: power supply failure
- LED flashes: module failure
LED Run, green LED
- The HIMax I/O module is supplied with power and is connected to the Termination Board (FTA) via a system cable.
LED Field, red LED
- The HIMax I/O module detects faults in the connection between HIMax I/O module and Termination Board (FTA).
Materialhousing: polycarbonate, 10 % glass fiber reinforced
Rated voltage24 V DC , in consideration of rated voltage of used isolated barriers
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Electromagnetic compatibilityNE 21:2012
For further information see system description.
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Degree of protectionIP20
Output typevolt-free contact
EC-Type Examination CertificateCESI 06 ATEX 022
Contact loading30 V DC, 1 A
Power dissipation≤ 500 mW , without modules
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Degree of protectionIEC 60529:2001
Connectionhazardous area connection (field side): spring terminals, blue
safe area connection (control side): HIMA system connector, 96-pin
power supply connection: pluggable spring terminals, black
SupplyRedundancy available. The supply for the modules is decoupled, monitored and fused.
Massapprox. 800 g
Dimensions266 x 200 x 163 mm (10.5 x 7.9 x 6.42 inch) , height including module assembly
in international format without spaces