Pepperl+Fuchs HiCTB32-HIM-RAC-SP-AI320X
Termination Board

Pepperl+Fuchs HiCTB32-HIM-RAC-SP-AI320X
  • System board for HIMA, HIMax
  • For 32-channel cards X-AI 32 01 or X-AI 32 02 (AI)
  • For 32 modules
  • Recommended modules: HiC2025 (AI), HiC2081 (TI)
  • 24 V DC supply
  • Hazardous area: spring terminals, blue
  • Safe area: HIMA system connector, 96-pin
Item Number: HiCTB32-HIM-RAC-SP-AI320X
1191.90
-
+
Total price: 1191.90
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Massapprox. 1300 g
Electromagnetic compatibilityNE 21:2012
For further information see system description.
Reverse polarity protectionyes
Degree of protectionIEC 60529:2001
EC-Type Examination CertificateCESI 06 ATEX 022
Dimensions432 x 200 x 163 mm (17 x 7.9 x 6.42 inch) , height including module assembly
ConnectionXG2: terminals 1, 3 (+); 2, 4 (-)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Rated voltage24 V DC , in consideration of rated voltage of used isolated barriers
Core cross-section0.25 ... 1.5 mm2 (24 ... 16 AWG)
Power dissipation≤ 500 mW , without modules
Output typevolt-free contact
Ripple≤ 10 %
IECEx approvalIECEx CES 06.0003
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Contact loading30 V DC, 1 A
Fusing4 A , in each case for 32 modules
Display elementsLED PWR1 (Termination Board power supply), green LED
LED PWR2 (Termination Board power supply), green LED
LED FAULT (fault indication), red LED
- LED lits: power supply failure
- LED flashes: module failure
LED Run, green LED
- The HIMax I/O module is supplied with power and is connected to the Termination Board (FTA) via a system cable.
LED Field, red LED
- The HIMax I/O module detects faults in the connection between HIMax I/O module and Termination Board (FTA).
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Materialhousing: polycarbonate, 10 % glass fiber reinforced
ConnectionXG2: terminals 5, 6
Degree of protectionIP20
SupplyRedundancy available. The supply for the modules is decoupled, monitored and fused.
Connectionhazardous area connection (field side): spring terminals, blue
safe area connection (control side): HIMA system connector, 96-pin
power supply connection: pluggable spring terminals, black

Comments

No comments yet