Pepperl+Fuchs HiD2022
SMART Transmitter Power Supply

Pepperl+Fuchs HiD2022
We ship to United States of America!

This item is out of production!

  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
  • Output 0/4 mA ... 20 mA current source
  • Up to SIL 2 acc. to IEC 61508
Item Number: HiD2022
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +

This item is out of production!

Check with the manager for a replacement.

CertificateCML 17 ATEX 3144X
Labelingspace for labeling at the front
Massapprox. 140 g
Output signal0/4 ... 20 mA (overload > 25 mA)
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Connection sidecontrol side
Load0 ... 650 andOmega;
Rated voltage18 ... 30 V DC bus powered via Termination Board
Display elementsLED
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Ripplemax. 50 andmicro;A rms
Codingpin 1 and 3 trimmed
For further information see system description.
Input signal0/4 ... 20 mA , current limit 27 mA
Safety Integrity Level (SIL)SIL 2
Signal typeAnalog input
Mountingon Termination Board
IECEx approvalIECEx CML 17.0072X
EquipmentSL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Power dissipation 1.4 W
EquipmentSL2: 5b(+), 7a(-); 1b(+), 3b(-)
Input resistancemax. 265 andOmega; SL2: 5b, 7a; 1b, 3b ; max. 330 andOmega; SL2: 5a, 7a; 1a, 3b
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Frequency rangefield side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB)
Rise time/fall time100 micro/s
Degree of protectionIP20
Deviationat 20 ?°C (68 ?°F), 0/4 ... 20 mA
10 andmicro;A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
ConnectionSL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Degree of protectionIEC 60529:2001
EquipmentSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Settling time200 micro/s
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Ripplewithin the supply tolerance
Available voltage 16 V at 20 mA , SL2: 5a(+), 5b(-); 1a(+), 1b(-)
Connection sidefield side
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Relative humidity5 ... 90 %, non-condensing up to 35 ?°C (95 ?°F)
Power consumption 2.6 W
EU-Type Examination CertificateCML 17 ATEX 2143X
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC

Buy Pepperl+Fuchs HiD2022 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is a fast-developing industrial automation supplier. We have a lot of parts in stock. We provide the fastest delivery. The products offered are always new and original from the manufacturer. Not only will you receive your parts quickly and at a fantastic price, but you will also have a dedicated Account Manager on hand to help you throughout the whole process. Thanks to us you will be able to get rid of the cooperation with many suppliers, which greatly accelerates and facilitates your work.