Pepperl+Fuchs HiD2036
Current Driver/Repeater
We ship to United States of America!
This item is out of production!
- 2-channel isolated barrier
- 24 V DC supply (loop powered)
- Current input/output 1.5 mA ... 50 mA
- Fire detector or I/P supply
- Accuracy 0.1 %
- Conformal coating
Item Number:
HiD2036
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
This item is out of production!
Check with the manager for a replacement.
Current | 1.5 ... 50 mA , loop powered |
Power dissipation | 0.7 W at 40 mA , 24 V (per channel) |
Certificate | PF 11 CERT 2109 X |
Current consumption | < 0.6 mA at 24 V and open circuit |
Characteristics | for fire and smoke detectors Uout = (Uin - 1.6) - (0.4 x Iout) 6 V < Uin < 25 V Uout = (25 - 1.6) - (0.4 x Iout) 25 V < Uin < 30 V |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Response time | 50 ms , 10 ... 90 % step change for I/P applications |
Connection | via input terminals |
Influence of temperature | < ?± 0.01 %/K |
Mass | approx. 140 g |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Influence of load | < ?± 0.3 % of full-scale value from 0 ... 750 andOmega; |
IECEx approval | IECEx TUN 04.0012 |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
Rated voltage | 6 ... 30 V DC loop powered , reverse polarity protected |
Mounting | on Termination Board |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
Linearity | < ?± 0.1 % of full-scale value (range 4 ... 20 mA) |
Labeling | space for labeling at the front |
Degree of protection | IP20 |
Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
Signal level | voltage drop 9.6 V at 20 mA and 500 andOmega; load (4 V at 4 mA) |
Signal | 1.5 ... 50 mA for fire and smoke detectors 4 ... 20 mA on a load of max. 750 andOmega; for I/P applications |
Repeat accuracy | < ?± 300 andmicro;A, 6 V < Uin < 25 V/1.5 mA < Iout < 50 mA |
Accuracy | < ?± 0.1 % of full-scale value (range 4 ... 20 mA) |
Signal type | Analog input/analog output |
Degree of protection | IEC 60529:2001 |
Load | 0 ... 750 andOmega; for I/P applications |
Ripple | max. 150 andmicro;A peak to peak for I/P applications |
Buy Pepperl+Fuchs HiD2036 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. offers factory automation products. We can offer you specific products which are not available from other suppliers. We provide delivery to all continents. We can give you a quick response and very good prices. We always communicate openly with our clients. We provide a personal approach to each client.
People also buy
Comments
No comments yet