Pepperl+Fuchs HiD2036
Current Driver/Repeater
This item is out of production!
- 2-channel isolated barrier
- 24 V DC supply (loop powered)
- Current input/output 1.5 mA ... 50 mA
- Fire detector or I/P supply
- Accuracy 0.1 %
- Conformal coating
Item Number:
HiD2036
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
This item is out of production!
Check with the manager for a replacement.
Current | 1.5 ... 50 mA , loop powered |
Power dissipation | 0.7 W at 40 mA , 24 V (per channel) |
Certificate | PF 11 CERT 2109 X |
Current consumption | < 0.6 mA at 24 V and open circuit |
Characteristics | for fire and smoke detectors Uout = (Uin - 1.6) - (0.4 x Iout) 6 V < Uin < 25 V Uout = (25 - 1.6) - (0.4 x Iout) 25 V < Uin < 30 V |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Response time | 50 ms , 10 ... 90 % step change for I/P applications |
Connection | via input terminals |
Influence of temperature | < В± 0.01 %/K |
Mass | approx. 140 g |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Influence of load | < В± 0.3 % of full-scale value from 0 ... 750 andOmega; |
IECEx approval | IECEx TUN 04.0012 |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
Rated voltage | 6 ... 30 V DC loop powered , reverse polarity protected |
Mounting | on Termination Board |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
Linearity | < В± 0.1 % of full-scale value (range 4 ... 20 mA) |
Labeling | space for labeling at the front |
Degree of protection | IP20 |
Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
Signal level | voltage drop 9.6 V at 20 mA and 500 andOmega; load (4 V at 4 mA) |
Signal | 1.5 ... 50 mA for fire and smoke detectors 4 ... 20 mA on a load of max. 750 andOmega; for I/P applications |
Repeat accuracy | < В± 300 andmicro;A, 6 V < Uin < 25 V/1.5 mA < Iout < 50 mA |
Accuracy | < В± 0.1 % of full-scale value (range 4 ... 20 mA) |
Signal type | Analog input/analog output |
Degree of protection | IEC 60529:2001 |
Load | 0 ... 750 andOmega; for I/P applications |
Ripple | max. 150 andmicro;A peak to peak for I/P applications |