Pepperl+Fuchs HiD2038
SMART Current Driver

Pepperl+Fuchs HiD2038

This item is out of production!

This Item is out of Production!

2-channel, 24 V DC supply

Item Number: HiD2038
717.00
-
+
Total price: 717.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

This item is out of production!

Check with the manager for a replacement.

This Item is out of Production!

Signal levelinput voltage drop < 4 V with field wiring intact
input current < 1.2 mA with field wiring open

Datasheet:

  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Current output up to 750 Omega- load
  • SMART I/P and valve positioners
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508
Degree of protectionIEC 60529
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Degree of protectionIP20
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Connection sidecontrol side
Mountingon Termination Board
Ripple15 mV eff
Rated current40 mA at 24 V, 20 mA output (per channel)
Massapprox. 140 g
ConnectionSL1: 6b
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Power dissipation0.85 W at 24 V (per channel)
Labelingspace for labeling at the front
IECEx approvalIECEx TUN 04.0012
Frequency range0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz) for use with SMART positioners using HART protocol
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Influence of load< В± 0.1 % of full-scale value from 0 ... 750 andOmega;
Linearity< В± 0.1 % of full-scale value
Display elementsLEDs
Line fault detectionbreakage, load > 100 kandOmega;, short-circuit, load < 70 andOmega;
Input/inputfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Influence of temperature< В± 0.01 %/K
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Response time50 ms , 10 ... 90 % step change
Input current4 ... 20 mA , reverse polarity protected
Connection sidefield side
Signal typeAnalog output
Load0 ... 750 andOmega;
Safety Integrity Level (SIL)SIL 2
Output typeopen collector transistor (internal fault bus)
EU-Type Examination CertificateCESI 02 ATEX 086
CertificatePF 11 CERT 2109 X
Accuracy< В± 0.1 % of full-scale value
Output signal4 ... 20 mA
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)

Comments

No comments yet

Write a comment