Pepperl+Fuchs HiD2082
Temperature Converter
This item is out of production!
- 2-channel isolated barrier
- 24 V DC supply (bus powered)
- Thermocouple, RTD or potentiometer input
- Usable as signal splitter (1 input and 2 outputs)
- Linearized output 4 mA ... 20 mA, sink/source or 1 V ... 5 V
- Sensor breakage detection
- Configurable by PACTware
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number:
HiD2082
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
This item is out of production!
Check with the manager for a replacement.
Mounting | on Termination Board |
Labeling | space for labeling at the front |
Control elements | DIP-switch |
Connection side | control side |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Signal type | Analog input |
Output I, II | analog, current or voltage output |
Connection side | field side |
IECEx approval | IECEx TUN 04.0012 |
Voltage | selectable within the range -100 ... 100 mV |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Current | 95 mA at 20.4 V and 63 mA at 30 V |
Connection | SL2: 5a(+), 1a(+), 1b(-), 5b(-); 7a(+), 3a(+), 3b(-), 7b(-) |
RTD | type Cu10, Cu50, Cu100, Pt10, Pt50, Pt100, Pt500, Pt1000, Ni100 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt50GOST, Pt1000GOST (P50353-92) |
Potentiometer | 0.1 ... 20 kandOmega; |
Configuration | via DIP switches via PACTware |
Certificate | PF 11 CERT 2109 X |
Power consumption | 1.95 W |
Display elements | LEDs |
Degree of protection | IEC 60529:2001 |
Connection | SL1: 6b |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
Output type | open collector transistor (internal fault bus) |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms |
Degree of protection | IP20 |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Ripple | within the supply tolerance |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Mass | approx. 140 g |
Input resistance | min. 1 MandOmega; (-100 ... 100 mV) |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |