Pepperl+Fuchs HiD2082
Temperature Converter

Pepperl+Fuchs HiD2082

This item is out of production!

  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Thermocouple, RTD or potentiometer input
  • Usable as signal splitter (1 input and 2 outputs)
  • Linearized output 4 mA ... 20 mA, sink/source or 1 V ... 5 V
  • Sensor breakage detection
  • Configurable by PACTware
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: HiD2082
921.48
-
+
Total price: 921.48
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

This item is out of production!

Check with the manager for a replacement.

Mountingon Termination Board
Labelingspace for labeling at the front
Control elementsDIP-switch
Connection sidecontrol side
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Signal typeAnalog input
Output I, IIanalog, current or voltage output
Connection sidefield side
IECEx approvalIECEx TUN 04.0012
Voltageselectable within the range -100 ... 100 mV
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Current 95 mA at 20.4 V and 63 mA at 30 V
ConnectionSL2: 5a(+), 1a(+), 1b(-), 5b(-); 7a(+), 3a(+), 3b(-), 7b(-)
RTDtype Cu10, Cu50, Cu100, Pt10, Pt50, Pt100, Pt500, Pt1000, Ni100 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt50GOST, Pt1000GOST (P50353-92)
Potentiometer0.1 ... 20 kandOmega;
Configurationvia DIP switches
via PACTware
CertificatePF 11 CERT 2109 X
Power consumption 1.95 W
Display elementsLEDs
Degree of protectionIEC 60529:2001
ConnectionSL1: 6b
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
EU-Type Examination CertificateCESI 02 ATEX 086
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Output typeopen collector transistor (internal fault bus)
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms
Degree of protectionIP20
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Ripplewithin the supply tolerance
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Massapprox. 140 g
Input resistancemin. 1 MandOmega; (-100 ... 100 mV)
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)

Comments

No comments yet