Pepperl+Fuchs HiD2824
Switch Amplifier

Pepperl+Fuchs HiD2824

This item is out of production!

  • 4-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Dry contact or NAMUR inputs
  • 4 relay contact outputs
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508
Item Number: HiD2824
438.40
-
+
Total price: 438.40
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

This item is out of production!

Check with the manager for a replacement.

Relative humidity5 ... 90 %, non-condensing up to 35 В°C (95 В°F)
Galvanic isolationEN 50178:1997
Line fault detectionbreakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value
Configurationvia DIP switches
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
IECEx approvalIECEx TUN 04.0012
Mountingon Termination Board
Labelingspace for labeling at the front
Connection sidefield side
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
EU-Type Examination CertificateCESI 02 ATEX 086
Rated current15 mA at 24 V, relay energized (per channel)
CertificatePF 11 CERT 2109 X
Output typeopen collector transistor (internal fault bus)
ConnectionSL1: 6b
Contact loading50 V DC / 0.5 A non-inductive
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Display elementsLEDs
Output/power supplyfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Massapprox. 140 g
Safety Integrity Level (SIL)SIL 2
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-)
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Response time20 ms
Switching pointcontact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Mechanical life107 switching cycles
Switching frequency< 10 Hz
ConnectionSL1: 8a, 7a; 10a, 9a; 10b, 9b; 8b, 7b
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Output/Outputfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Connectable sensor typespotential free contact or proximity sensor
Control elementsDIP-switch
Power dissipation0.35 W at 24 V (per channel)
Outputsignal: relay SPST per channel, phase selectable
Signal typeDigital Input
Degree of protectionIP20
Connection sidecontrol side
Codingpin 1 and 2 trimmed
For further information see system description.
Degree of protectionIEC 60529:2001

Comments

No comments yet