Pepperl+Fuchs HiD2824
Switch Amplifier
This item is out of production!
- 4-channel isolated barrier
- 24 V DC supply (bus powered)
- Dry contact or NAMUR inputs
- 4 relay contact outputs
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC 61508
Item Number:
HiD2824
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
This item is out of production!
Check with the manager for a replacement.
Relative humidity | 5 ... 90 %, non-condensing up to 35 В°C (95 В°F) |
Galvanic isolation | EN 50178:1997 |
Line fault detection | breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value |
Configuration | via DIP switches |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
IECEx approval | IECEx TUN 04.0012 |
Mounting | on Termination Board |
Labeling | space for labeling at the front |
Connection side | field side |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
Rated current | 15 mA at 24 V, relay energized (per channel) |
Certificate | PF 11 CERT 2109 X |
Output type | open collector transistor (internal fault bus) |
Connection | SL1: 6b |
Contact loading | 50 V DC / 0.5 A non-inductive |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Display elements | LEDs |
Output/power supply | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
Mass | approx. 140 g |
Safety Integrity Level (SIL) | SIL 2 |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-) |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Response time | 20 ms |
Switching point | contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA |
Mechanical life | 107 switching cycles |
Switching frequency | < 10 Hz |
Connection | SL1: 8a, 7a; 10a, 9a; 10b, 9b; 8b, 7b |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Output/Output | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
Connectable sensor types | potential free contact or proximity sensor |
Control elements | DIP-switch |
Power dissipation | 0.35 W at 24 V (per channel) |
Output | signal: relay SPST per channel, phase selectable |
Signal type | Digital Input |
Degree of protection | IP20 |
Connection side | control side |
Coding | pin 1 and 2 trimmed For further information see system description. |
Degree of protection | IEC 60529:2001 |
People also buy
Comments
No comments yet