Sensor output interface terminal

- 1-channel terminal amplifier
- NAMUR sensor input
- DC 24 V supply voltage
- Standard interface for prevention of signal transmission errors
- Switching status indicator, yellow LED
- Lead breakage monitoring: The lead breakage monitoring can be disconnected by bridging terminals 1 and 3
- Short-circuit proof electronic output
- Low noise sensitivity
- Compact terminal housing
- Clips onto standard 35 mm rail to DIN EN 50 022
- Degree of protection IP20

Item Number:
KCD2-EL
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Datasheet
- Alternative numbers
- Comments
Connection | self-opening apparatus connection terminals, max. core cross-section 0.34 ... 2.5 mm2 |
Line fault detection | with |
Switching frequency | 1 kHz |
Dimensions | 20x60x40 (in mm) |
Noise immunity | EN 61326-1:2013 |
Connection | terminals 1+, 2- |
Sensor supply | 8 V DC |
Trip value | 1 kHz |
Ripple | 10 % |
Degree of protection | IP20 |
Connection | terminal 4- |
Connectable sensor types | NAMUR |
Short-circuit current | approx. 8 mA |
Switching point | 1.2 ... 2.1 mA hysteresis approx. 0.2 mA |
Degree of protection | EN 60529:2000 |
Signal level | UB - 1.8V |
Current | 200 mA short-circuit protected |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Operating voltage | 10 ... 30 V DC |
Transistor | NPN |
MTTFd | 1612 a |
Operating current | approx. 22 mA |
Mass | 60 g |
Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
Pulse length/pulse interval | 0.5 ms / 0.5 ms |
Mode of operation | NO contact |
LED yellow | switch output lead breakage: LED off, output locked |